Product Description 

The DSC-1616 is a fully programmable, Native BACnet

 

Building Controller that communicates on Twisted Pair 

Ethernet 10-BaseT using BACnet IP and BACnet over 

Ethernet, or on an RS-485 LAN using the BACnet MS/TP 

protocol.  

The controller includes an easy to mount enclosure and is 

designed for a wide range of applications requiring no more 

than 16 inputs and 16 outputs, including but not limited to Roof 

Top Units, Air Handlers, Boilers or Chillers, etc.  A second RS-

485 port may be configured as an MS/TP SubLAN or a 

LINKnet network that supports up to 12 Delta BACstats or 

other Delta LINKnet controllers. 

The 16 universal inputs are jumper configurable and the 16 

analog outputs have an option of coming with monitored Hand-

Off-Auto switches. 

 

Important Information  

 

 

ORCAview OWS and controller firmware must all be of the same version number to 

be compatible. When upgrading any of these products from older versions (i.e. 3.22 or 3.30), 

you must upgrade all the remaining products. Exception: UL 864 model, DSC-1616E-UL864 

can be used with V3.33 

Package Contents 

 

Product: DSC-1616 

 

DSC-1616 Installation Guide 

Related Documents 

 

Delta Controls Wiring Guidelines 

 

ORCAview Operator Guide 

 

ORCAview Technical Reference Manual  

 

Release Notes for related Firmware 

 

and V3.40 firmware.

Summary of Contents for DSC-1616

Page 1: ...may be configured as an MS TP SubLAN or a LINKnet network that supports up to 12 Delta BACstats or other Delta LINKnet controllers The 16 universal inputs are jumper configurable and the 16 analog out...

Page 2: ...statically sensitive device Proper ESD protection ground strap should be used when installing this product so that damage to the product does not occur Danger of explosion if the battery is incorrect...

Page 3: ...ing The DSC 1616 includes a plastic enclosure that can be quickly mounted with two screws not provided This controller should be mounted in an appropriate location within packaged equipment or another...

Page 4: ...Delta Controls Page 4 of 12 Board Layout...

Page 5: ...a Subnet of similar controllers This is the setting when the controller is connected to a BACnet MS TP network with other Subnet controllers Note This also determines where the DIP or MAC address is m...

Page 6: ...gned to use a 24 VAC Class 2 power supply The proper specified cabling must be used 18 16 AWG 2 conductor wire A single transformer may be used to power multiple controllers and or auxiliary field dev...

Page 7: ...he proper specified cabling must be used to ensure reliable communications 22 AWG twisted pair 100 120 ohms impedance 17 pF ft or lower capacitance with a braided or aluminum foil shield Controllers s...

Page 8: ...ept the signal used by the input device Place the jumper for each input in the correct location on the Input Type Selector Block The diagram to the right shows the factory default selection of 10 K 4...

Page 9: ...good both LEDs will flash at a high rate Network NET2 MS TP RS485 Communication Status Indicators The green LED flashes to indicate when the controller is transmitting out the port and the red LED fl...

Page 10: ...ation 76800 bps Maximum of 12 LINKnet controllers including up to two DFM controllers Serial RS 232 BACnet PTP Communication 9600 19200 38400 default Service Port RJ 11 Jack Used with Delta Controls s...

Page 11: ...Line Harmonics Class A EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN 50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Immunity Level B EN 61000 4 3 1996 R...

Page 12: ...l interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at...

Reviews: