Cautions or Warnings 

 

This controller is an Electro-statically sensitive device. Proper ESD protection (ground strap) 
should be used when installing this product so that damage to the product does not occur. 

Danger of explosion if the battery is incorrectly replaced. Replace only with the same or equivalent 
type recommended by the manufacturer. Dispose of used batteries according to the 
manufacturer’s instructions. Replace the battery with type CR2032. 

Equipment damage or loss of data may occur if these procedures are not followed as specified. 

Installations requiring CE conformance

: All wiring for CE rated products must use an extra low 

voltage (SELV) or protective extra low voltage (PELV) transformer. Use safety-isolating 
transformers, (Class II transformer) per EN61558. The transformer must be rated for 100% duty 
cycle. 

Mounting 

The DFM-1616 includes a plastic enclosure that can be quickly mounted with two screws (not provided). This 
controller should be mounted in an appropriate location within packaged equipment or another enclosure that 
meets code requirements. 

 

Page 2 of 10 

Summary of Contents for DFM-1616

Page 1: ...intended to fit a range of Central Plant type applications requiring up to 48 Inputs and 48 Outputs When the DFM 1616 is combined with the ASM 24E it forms a controller suited for Elevator Control ap...

Page 2: ...ry with type CR2032 Equipment damage or loss of data may occur if these procedures are not followed as specified Installations requiring CE conformance All wiring for CE rated products must use an ext...

Page 3: ...Document Edition 2 4 Board Layout Page 3 of 10...

Page 4: ...set the address simply move the switches that add up to the controllers desired address to the ON position Example If the controller is to be address 5 on the network set the switch numbered 4 and th...

Page 5: ...sformer may be used to power multiple controllers and or auxiliary field devices actuators etc provided the following conditions are met All devices MUST be wave rectified Mixing power between wave an...

Page 6: ...hen 100 ft of cable length do not require network terminators LINKnet Controller Outputs with Communication Failure When using this controller special consideration must be given to the fail value of...

Page 7: ...turns on to indicate that the controller has power applied Scan CPU Scan Indicator This red LED flashes at a rate relative to the CPU scan rate Network NET1 LINKnet RS485 Communication Status Indicato...

Page 8: ...puts 16 Universal Inputs 10 bit jumper configurable for the following input types 0 5 VDC 0 10 VDC 10 K Thermistor Dry Contact using 10 K Thermistor jumper setting 4 20 mA Outputs 16 Universal Outputs...

Page 9: ...999 Power Line Harmonics Class A EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN 50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Immunity Level B EN 61000 4...

Page 10: ...accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case t...