Storage
Half sine shock on all six sides of 71G +/- 5% with a pulse duration
of 2ms +/- 10%
Altitude
Operating
-15.2m to 3048m (-50 to 10,000ft)
Note: For altitudes above 2950ft, the maximum temperature is
derated 1°F/550ft
Storage
-16 to 10,600m (-50 to 35,000ft)
Airborne contaminant level
Class G1 or lower as defined by ISA-S71.04-1985 (G1 maximum corrosive contaminant levels
measured at ≤ 50% relative humidity)
5.4
ENERGY STAR Compliance
ENERGY STAR
®
qualified configurations can be accessed from the
ENERGY STAR Compliance results
landing page on Dell.com.
5.5
Thermal
The Dell™ PowerEdge™ M915 is the first blade to support ≥130W processors in a 4-socket
configuration. Larger heat sinks provide increased cooling capability, which enables 4-socket 140W
configurations without restrictions on external ambient temperature.
The M915 thermal solution includes the following features:
Optimized airflow impedance for individual blade and chassis-level airflow balancing
Custom top cover air baffling prevents DIMM airflow bypass to balance airflow and maintain
proper DIMM cooling
Custom-designed heat sinks maintain processor and chipset temperatures within thermal
design targets
Highly optimized fan control algorithm:
o
Base fan speeds are a function of hardware configuration and ambient temperature to
minimize airflow for a given environment
o
PID fan control algorithms are used for processors, DIMMs, and NDC I/O thermal
sensors to maintain appropriate thermal margin while minimizing component over-
cooling
o
NDC I/O sensor algorithm allows for lower fan speeds by sensing the air temperature
near the exhaust of the blade while maintaining proper airflow and cooling for the
mezzanine cards
o
The highest fan-speed request from the above algorithms is used to set the
appropriate fan speed for the blade
o
The ambient and hardware configuration sets the minimum fan speed—other
algorithms increase fan speed as needed to maintain proper cooling