Configuring the EMP
7
Temperature and humidity measurements are displayed in a graduated bar (see Figure 6). The red
zones to the left and right of the bar represent the low and high thresholds. If notification is turned on,
an alarm is generated when the measured value enters one of these zones. The cursor indicates the
current reading.
Figure 6. Graduated Bar (Humidity Bar Shown)
3
Click
Reset Min/Max
to display the time-stamped minimum and maximum since the previous reset
for temperature or humidity.
NOTE:
The EMP is factory-calibrated, but you can apply an offset to adjust the measurement.
4
Click
Calibrate
for temperature or humidity to open the Offset page.
5
Enter the Offset value and click
Apply
or
Save
.
NOTE:
Input #1 and Input #2 display the status of the two contacts acquired by the EMP. The last status change of
each contact is time stamped.
Before the status of the contact closures display, you must configure and enable this feature on the Environment
Settings page.
High Threshold
Red Zone
Low Threshold
Red Zone
Current Reading