Tile placement
You must understand tile placement to ensure that the array is positioned properly and
to allow sufficient room for service and cable management.
When placing the array, consider the following:
l
Typical floor tiles are 24 in. (61 cm) by 24 in. (61 cm).
l
Typical cutouts are:
n
8 in. (20.3 cm) by 6 in. (15.2 cm) maximum.
n
9 in. (22.9 cm) from the front and rear of the floor tile.
n
Centered on the tiles, 9 in (22.9 cm) from the front and rear and 8 in (20.3)
from sides.
l
Maintain a .25 in. (.64 cm) gap between bays.
l
Service area of 42 in (106 cm) for the front and 30 in (76 cm) for the rear on the
system bays.
The following figure provides tile placement information for all VMAX All Flash arrays
(with doors).
Figure 8 Placement with floor tiles, VMAX 450F, VMAX 850F, VMAX 950F
Rear
A
A
System
bay
System
bay
A
System
bay
A
System
bay
Front
F
l
o
o
r
T
i
l
e
Position VMAX 450F, VMAX 850F, VMAX 950F Bays
Tile placement
55