Table 25 Maximum altitude specifications
Maximum altitude
Specifications
Operating
3048 m (10,000 ft)
Storage
12,000 m (39,370 ft)
If the operating temperature of a system is up to 35°C (95°F), the maximum temperature is
reduced by 1°C/300 m (1°F/547 ft) above 950 m (3,117 ft). If the operating temperature of a
system is 35 °C–40 °C (95 °F–104 °F), the maximum temperature is reduced by 1°C/175 m
(1°F/319 ft) above 950 m (3,117 ft). If the operating temperature of a system is 40 °C–45 °C
(104–113 °F), the maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m
(3,117 ft).
Table 26 Operating temperature derating specification
Operating temperature derating
Specifications
Up to 35°C (95°F)
Maximum temperature is reduced by 1°C/300 m
(1°F/547 ft), above 950 m (3,117 ft).
35–40 °C (95–104 °F)
Maximum temperature is reduced by 1°C/175 m
(1°F/319 ft), above 950 m (3,117 ft).
40–45 °C (104 °F–113 °F)
Maximum temperature is reduced by 1°C/125 m
(1°F/228 ft), above 950 m (3,117 ft).
Standard operating temperature
The standard operating temperature for altitude less than 950 m or 3117 ft ranges 10 °C–35°C
with no direct sunlight on the equipment.
Note:
The 2.5-inch hard drive chassis supports a maximum of 145 W processors.
Table 27 Standard operating temperature specifications
Standard operating temperature
Specifications
Continuous operation (for altitude less
than 950 m or 3117 ft)
10 °C–35°C (50 °F–95°F) with no direct sunlight
on the equipment.
Expanded operating temperature
When the system is in continuous operation, the expanded operating temperature ranges 5 °C–
40°C at 5% to 85% RH with 29°C dew point. NOTE: Outside the standard operating temperature
(10 °C–35°C), the system can operate continuously in temperatures as low as 5°C and as high as
40°C. For temperatures 35 °C – 40°C, derate maximum allowable temperature by 1°C per 175 m
above 950 m (1°F per 319 ft). When the system is operating at < 1% of annual operating hours, the
expanded operating temperature is –5 °C–45°C at 5% to 90% RH with 29°C dew point. NOTE:
Outside the standard operating temperature (10 °C–35°C), the system can operate down to –
5°C or up to 45°C for a maximum of 1% of its annual operating hours. For temperatures 40 °C–
45°C, derate maximum allowable temperature by 1°C per 125 m above 950 m (1°F per 228 ft).