10
Enter the correct time and date in the System Setup
Time
and
Date
fields.
11
Exit the System Setup.
Optional internal USB memory key
NOTE:
To locate the internal USB port on the system board, see the
System board jumpers and connectors
section.
Replacing the optional internal USB memory key
Prerequisites
CAUTION:
To avoid interference with other components in the server, the maximum permissible dimensions of the USB memory
key are 15.9 mm wide x 57.15 mm long x 7.9 mm high.
1
Follow the safety guidelines listed in
2
Power off the system and all attached peripherals.
3
Disconnect the system from the electrical outlet, and disconnect the peripherals.
4
Ensure that all internal cables are routed correctly and connected, and no tools or extra parts are left inside the system.
5
, remove
6
Remove the
.
7
Remove the system from the rack and place it on an ESD work bench. For more information, see the Rail Installation Guide available at
.
8
.
9
10
If installed,
remove the low profile expansion card riser
Steps
1
Locate the USB port or USB memory key on the system board.
To locate the USB port, see the
.
2
If installed, remove the USB memory key from the USB port.
Figure 116. Removing the internal USB memory key
1
USB memory key
2
USB port
3
Insert the replacement USB memory key into the USB port.
142
Installing and removing system components