CPU
TDP
Cores
24 x drives
16 x drives
8 x drives
4 x drives
No BP
7262
155
8
25
25
25
25
30
7282
120
16
30
30
30
35
35
7252
120
12
30
30
30
35
35
7272
120
8
30
30
30
35
35
NOTE:
• 85C Optics Transceiver is required for OCP cards
• Additional thermal restrictions are required for 128GB LRDIMM and GPU configuration
Table 52. Maximum continuous operating temperature for dual processor with 3.5-inch Direct drive configuration - Air
cooled
CPU
TDP
Cores
12 x drives
8 x drives
4 x drives
7742
225
64
Not Supported
Not Supported
Not Supported
7702
200
64
Not Supported
Not Supported
Not Supported
7542
225
32
Not Supported
Not Supported
Not Supported
7502
180
32
Not Supported
Not Supported
Not Supported
7402
180
24
Not Supported
Not Supported
Not Supported
7452
155
32
Not Supported
Not Supported
Not Supported
7352
155
24
Not Supported
Not Supported
Not Supported
7302
155
16
Not Supported
Not Supported
Not Supported
7262
155
8
Not Supported
Not Supported
Not Supported
7282
120
16
20
20
20
7252
120
12
20
20
20
7272
120
8
20
20
20
NOTE:
• 85C Optics Transceiver is required for OCP cards
• Additional thermal restrictions are required for 128GB LRDIMM and GPU configuration
Table 53. Maximum continuous operating temperature for dual processor with 2.5-inch direct / 2.5-inch NVMe drive
configuration - Liquid cooled
CPU
TDP
Cores
24 x drives
16 x drives
8 x drives
4 x drives
No BP
7742
225
64
35
35
35
35
35
7702
200
64
35
35
35
35
35
7542
225
32
35
35
35
35
35
7502
180
32
35
35
35
35
35
7402
180
24
35
35
35
35
35
7452
155
32
35
35
35
35
35
7352
155
24
35
35
35
35
35
7302
155
16
35
35
35
35
35
7262
155
8
35
35
35
35
35
7282
120
16
35
35
35
35
35
Technical specifications
89