Maximum shock specifications
Table 9. Maximum shock specifications
Maximum shock
Specifications
Operating
24 executed shock pulses 6 G in the positive and negative x, y, z axis up to 11
ms (four pulses on each side of the system)
Storage
Six consecutively executed shock pulses of 71 G in the positive and negative
x, y, z axes up to 2 ms (one pulse on each side of the system)
Maximum altitude specifications
Table 10. Maximum altitude specifications
Maximum altitude
Specifications
Operating
3,048 m (10,000 ft)
Storage
12,000 m (39,370 ft)
Operating temperature de-rating specifications
Table 11. Operating temperature de-rating specifications
Operating temperature de-rating
Specifications
Up to 35°C (95°F)
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m
(3,117 ft).
35°C to 40°C (95°F to 104°F)
Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m
(3,117 ft).
40°C to 45°C (104°F to 113°F)
Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m
(3,117 ft).
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility of the customer.
Table 12. Particulate contamination specifications
Particulate contamination
Specifications
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a
95% upper confidence limit.
12
Installation and Service Manual
Technical specifications