Table 8 DLm physical specification for a single cabinet
Description
Measurements
Height
76.66 in (194.7 cm)
Width
24.02 in (61.0 cm)
Depth
41.88 in (106.4 cm)
Clearance for service and airflow
Front
42 in (106.7 cm)
Rear
42 in (106.7 cm)
Top
18 in (45.7 cm)
a. With trim kit (optional) attached.
DLm power requirements
This section describes the North American electrical specifications, power cables,
connectors, and extension cords for a DLm configuration.
The following table summarizes power requirements for the possible cabinets that are
associated with a DLm8500 system.
Table 9 North American, single-phase, electrical specifications
Specification
Requirements
Input voltage
200 V AC–240 V AC -10%/+10% single-phase
Frequency
50 Hz–60 Hz
Circuit breakers
30 A
Power zones
Two
Onsite power requirements (for each cabinet)
l
Two single-phase drops each for:
DLm8500 VTEC cabinet
Data Domain cabinet
Note:
For required power drops, see the
applicable documentation.
Power distribution panel connectors
NEMA L6-30P. Facility power mating
receptacle is L6-30R.
Before delivery, the customer must supply and install the required receptacles to zone
A and zone B power for the DLm cabinets. The following figure shows 2-drop and 4-
drop power cabling.