Chapter
Ⅲ
Installation and Wiring
Page 11
Chapter III Installation and Wiring
3.1 Installation Site and Space
Installation site:
Warning
1. Avoid direct sunlight and outdoor direct use.
2. Don’t use it under corrosive gas and liquid environment.
3. Don’t use it under oil fog and splashing water environment.
4. Don’t use it under salt fog environment.
5. Don’t use it under raining and moist environment.
6. Please equip the unit with filters device if metal dust or fiber
wadding existing in air.
7. Avoid power noise, such as electric welding machine and
high-power electrical equipment, which can impact operation of
the equipment.
8. Radioactive materials can influence use of the Product.
9. Avoid flammable materials, thinner and solvent.
Environment
Environment temperature: -10
℃
~+40
℃
Storage temperature: -20
℃
~+65
℃
Environment humidity: 90% RH at maximum (noncondensing)
Height: Under 1,000 m. Reduce capacity by 1% for every 100
m after the altitude exceeds 1,000 m.
Vibration: No greater than 5.9 m/s
2
(0.6 g) at maximum.
Installation direction: Please install the product vertically in
order not to affect the heat dissipation effect of frequency
inverter.
For sound performance and long service life, the frequency inverter shall be
installed according to the above installation environment suggestions to prevent
damages.