Section 2
Installation
Part Number: 9291493 REV00 06/20 11
OPTION DIMENSIONS
Option
Length
Depth
Height
Self Contained Combination Hot/Cold Food Wells
N8630P
30.75”
(78cm)
26”
(66cm)
26.4”
(67cm)
N8643P
43.5”
(111cm)
26”
(66cm)
26.4”
(67cm)
N8656P
56.25”
(143cm)
26”
(66cm)
26.4”
(67cm)
N8669P
69”
(175cm)
26”
(66cm)
26.4”
(67cm)
N8681P
81.75”
(208cm)
26”
(66cm)
26.4”
(67cm)
Individually Controlled Energy Savings Heated Food Wells
1 Well DESP
17.89”
(45cm)
26”
(66cm)
9.5”
(24cm)
2 Well DESP
31.76”
(81cm)
26”
(66cm)
9.5”
(24cm)
3 Well DESP
45.63”
(116cm)
26”
(66cm)
9.5”
(24cm)
4 Well DESP
59.50”
(151cm)
26”
(66cm)
9.5”
(24cm)
5 Well DESP
73.37”
(186cm)
26”
(66cm)
9.5”
(24cm)
6 Well DESP
87.24”
(222cm)
26”
(66cm)
9.5”
(24cm)
Electrical Service
DANGER
Check all wiring connections, including factory
terminals, before operation. Connections can become
loose during shipment and installation.
n
Warning
This appliance must be grounded and all field wiring
must conform to all applicable local and national
codes. Refer to rating plate for proper voltage. It is the
responsibility of the end user to provide the disconnect
means to satisfy the authority having jurisdiction.
VOLTAGE
All electrical work, including wire routing and grounding,
must conform to local, state and national electrical codes.
The following precautions must be observed:
• The equipment must be grounded.
• A separate fuse/circuit breaker must be provided for
each unit.
• The maximum allowable voltage variation is ±10% of
the rated voltage at equipment start-up (when the
electrical load is highest).
• Check all green ground screws, cables and wire
connections to verify they are tight before start-up.
GROUND FAULT CIRCUIT INTERRUPTER
Ground Fault Circuit Interrupter (GFCI/GFI) protection is
a system that shuts down the electric circuit (opens it)
when it senses an unexpected loss of power, presumably
to ground. Welbilt does not recommend the use of GFCI/
GFI circuit protection to energize our equipment. If code
requires the use of a GFCI/GFI then you must follow the
local code. The circuit must be dedicated, sized properly
and there must be a panel GFCI/GFI breaker. We do not
recommend the use of GFCI/GFI outlets to energize our
equipment as they are known for more intermittent
nuisance trips than panel breakers.