12

Delfield

®

Operation N8100B, N8100NB & N8100-BR

N8100 Series mechanically cooled cold pans are adjusted 
at the factory to provide proper operation without any further 
adjustments.  However, if it is necessary to adjust the 
temperature, the control is located in the machine compartment.  
Turn the knob clockwise as indicated on the control.  Settings 
are from 1 thru 7 (7 being the coldest).  Adjustments should 
be made gradually.  Several small adjustments will be more 
effective than one large adjustment.  It may take an hour or 
longer to realize the temperature change depending on the 
application and location of the unit.

These units are not designed to cool warm food products.  Items 
should be placed in the unit pre-cooled at least to the desired 
holding temperature, if not slightly colder.  In some applications, 
a gradual warming of product may occur, particularly at the 
exposed top of the product.  Stirring or rotation of the product 
may be necessary to maintain overall temperature.  

Warming of food product can occur very quickly outside of the 
unit.  When loading or rotating product, avoid leaving food items 
in a non-refrigerated location for any length of time to prevent 
warming or spoilage.

The temperature control is used to turn the unit on and off as 
well as control the temperature of the cold pan.  The settings 
range from 1 through 7 (7 being the coldest).  To turn the cold 
pan off, turn the knob to the 

OFF

 position.

If the cold pan is to be used with ice, it is recommended that 
the optional perforated bottoms be used.  These will allow ice 
to melt properly.

The unit must be turned off when not in use or overnight for 
defrosting and cleaning.

Operation N8100-FA

N8100-FA Series forced air mechanically cooled cold pans come 
equipped with 115-volt, 60 Hertz, single phase refrigeration 
units.  The refrigeration valves are open and ready to operate 
as soon as the power supply cord is plugged into the standard 
115-volt, grounded electrical outlet.

Pressure Control

The temperature is controlled by an adjustable pressure control 
located in the machine compartment and adjustable control has 
the word COLDER near the knob, with an arrow to indicate the 
adjustment direction.  This control is field adjustable and does 
not require a service agent.  If you have any questions, feel free 
to contact the Delfield Service Department at (800) 733-8829.

In attempting to adjust the pressure control, 
you can do damage to the unit by accidentally 
adjusting the differential.  Delfield is not 
responsible for charges incurred while adjusting 
the pressure control.

Food in the N8100-FA pans should not be loaded 
in such a way as to interfere with the air curtain 
flowing over the cold pans.

Ruby Tuesday Salad Bar Service and Installation Manual

For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com

8

DEFROST TIMER

Defrost Timer

Every 2 hours for 15 minutes.

18000 and CTP-NB Series Service and Installation Manual

5

For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfi eld.com

Refrigerant Charges For 18000 Series Units:

18648-PTB  . . . . . . . . . . . . . . . . . . . . . . .16 oz.

18660-PTB  . . . . . . . . . . . . . . . . . . . . . . .24 oz.

18672-PTB  . . . . . . . . . . . . . . . . . . . . . . .32 oz.

18691-PTB  . . . . . . . . . . . . . . . . . . . . . . .32 oz.

18699-PTB  . . . . . . . . . . . . . . . . . . . . . . .48 oz.

186114-PTB  . . . . . . . . . . . . . . . . . . . . . .48 oz.

18648-BUC . . . . . . . . . . . . . . . . . . . . . . .16 oz.

18660-BUC . . . . . . . . . . . . . . . . . . . . . . .16 oz.

18672-BUC . . . . . . . . . . . . . . . . . . . . . . .16 oz.

18691-BUC . . . . . . . . . . . . . . . . . . . . . . .16 oz.

18699-BUC . . . . . . . . . . . . . . . . . . . . . . .24 oz.

186114-BUC . . . . . . . . . . . . . . . . . . . . . .24 oz.

Refrigerant Charges For CTP-NB Series Units:

CTP8146-NB . . . . . . . . . . . . . . . . . . . . . . .8 oz.

CTP8160-NB . . . . . . . . . . . . . . . . . . . . . . .8 oz.

CTP8175-NB . . . . . . . . . . . . . . . . . . . . . . .8 oz.

Pressure Control Settings

The factory recommended low-pressure control settings for 18000-PTB’s are:

 55# cut-in and 30# cut-out to maintain 

proper temperature for product in the rail. The interior temperature is controlled by the thermostat mounted on the 

evaporator coil housing. 

The factory recommended low-pressure control settings for 18000-BUC’s are: 

82# cut-in and 57# cut-out to maintain 

proper temperature. 

REFRIGERANT CHARGES AND PRESSURE CONTROL SETTINGS

All Delfield refrigerated models come equipped with 

115-volt, 60 cycle, single phase refrigeration units. The 

refrigeration valves are open and ready to operate as soon 

as the power supply cord is plugged into the standard 115-

volt, grounded electrical outlet.

Pressure Control

The temperature is controlled by an adjustable pressure 

control located in the machine compartment. An adjustable 

control has the word 

COLDER

 near the knob, with an arrow 

to indicate the adjustment direction. These controls are 

field adjustable and do not require a service agent. If you 

have any questions, feel free to contact the Delfield Service 

Department.

 In attempting to adjust the pressure control, 

you can do damage to your unit by accidentally 

adjusting the differential. Please make small 

incremental adjustments if a temperature 

adjustment is necessary, please contact the 

service department at Delfield (800) 733-8821 

or your local service agent. Delfield is not 

responsible for charges incurred while having 

the pressure control adjusted.

PRESSURE CONTROL SETTINGS

30 psi (207 kPa) differential

80 psi (552 kPa) cut-in

50 psi (345 kPa) cut-out

Summary of Contents for 8100-EF

Page 1: ...Before Use Please Save These Instructions N8000 N8000 R N8100B N8100 BR N8100 FA 8100 EF N8200 N8200G N8600 N8700 D N8700 R N8800 Drop Ins Service Installation and Care Manual Please read this manual...

Page 2: ...perate This Equipment WARNING This Appliance Is Not Intended For Use By Persons Who Lack Experience Or Knowledge Unless They Have Been Given Supervision Or Instruction Concerning Use Of The Appliance...

Page 3: ...ld be noted and reported to the delivering carrier immediately 2 If damaged open and inspect the contents with the carrier 3 In the event that the exterior is not damaged yet upon opening there is con...

Page 4: ...ge Always have the serial number of your unit available when calling for parts or service This manual covers only standard 8000 series units If you have a custom designed unit you should contact our p...

Page 5: ...oz 5 15P 3 N8100BR Series Curved Self Contained Mechanically Cooled Pans R134A Model L D H Counter Cutout Dimensions V Hz Ph Amps H P BTU Evap BTU TD TEMP Sys Cap Ship Weight Refrig Charge NEMA Plug 1...

Page 6: ...6 66cm 23 25 59 1cm 17 x 25 43 2cm x 63 5cm 115 60 1 7 5 1 4 204 19 50 15 928 169lbs 77kg 24 0oz 5 15P 1 8132 EF 31 76 80 7cm 26 66cm 23 25 59 1cm 30 75 x 25 78 1cm x 63 5cm 115 60 1 7 5 1 4 379 26 42...

Page 7: ...9 26 42 7 1112 219lbs 99kg 24 0oz 5 15P N8245G 45 63 115 9cm 25 87 65 7cm 19 48 3cm 44 63 x 25 113 4cm x 63 5cm 115 60 1 7 5 1 4 569 35 36 1 1259 284lbs 129kg 24 0oz 5 15P N8259G 59 5 151 1cm 25 87 65...

Page 8: ...Model L D H Counter Cutout Dimensions Control Panel Cutout Dimensions V Hz Ph Amps Ship Weight 12 x20 Pans N8717 D 17 88 45 4cm 26 66cm 9 5 24cm 16 88 X 25 42 8cm x 63 5cm 7 00 x 4 62 x 7 00 17 8cm x...

Page 9: ...56 50cm 25 10 64cm 25 10 64cm 85 95 172 50 172 50 172 50 85 95 25 00 64cm 25 00 64cm 25 00 64cm 25 00 64cm 15 73 40cm 13 78 35cm 13 78 35cm 15 73 40cm 25 10 64cm 13 78 35cm 15 73 40cm 19 56 50cm 85 9...

Page 10: ...the unit is connected to the proper power source A protected circuit of the correct voltage and amperage must be run for con nec tion of the line cord Some units have an ON OFF switch located behind...

Page 11: ...and N8700 R series units have 48 121 9cm of conduit and N8800 Series units have 24 61 0cm of conduit between the pans and the remote control panel to facilitate this installation Plumbing N8700 D N87...

Page 12: ...e Delfield Service Department at 800 733 8829 In attempting to adjust the pressure control you can do damage to the unit by accidentally adjusting the differential Delfield is not responsible for char...

Page 13: ...nit Turn the unit on approximately two hours prior to use to allow for ample cool down time The unit must be turned off when not in use or overnight for defrosting and cleaning There is a switch on th...

Page 14: ...es about one hour To assure maximum compressor life do not switch from hot to cold operation without allowing a cool down period Never switch from hot to cold operation while hot water remains in the...

Page 15: ...overs on pans when not serving to prevent food from drying out Wet Operation Fill the food well with a minimum of 2 5 1cm of water and cover with lid or empty pan To preheat water set temperature cont...

Page 16: ...ing chlorides will damage the protective film of the stainless steel Chlorides are also commonly found in hard water salts and household and industrial cleaners If cleaners containing chlorides are us...

Page 17: ...delfield com Delfield Upright Air Diffuser With Air Deflector Black Airflow Extrusions Perforated Pan Clip Adapter Bars Coil Assy Cover Plexiglas End Caps Unit Assembly N8100 FA Wiring Diagram N8100 F...

Page 18: ...3210 www delfield com 18 Delfield Wiring Diagram N8100B N8100NB N8100 BR COOLING T STAT CONDENSER FAN COMPRESSOR 115V L1 N G S C R ON OFF SWITCH CONDENSER FAN COMPRESSOR 115V S C R L1 N G COOLINGT STA...

Page 19: ...N8000 Series Drop In Installation and Operation Manual 19 For customer service call 800 733 8829 800 733 8821 Fax 989 773 3210 www delfield com Delfield Wiring Diagram N8643 N8656 Wiring Diagram N8630...

Page 20: ...peration Manual For customer service call 800 733 8829 800 733 8821 Fax 989 773 3210 www delfield com 20 Delfield Wiring Diagram N8669 N8681 Wiring Diagram N8800 208 230V THERMOSTAT LI G L2 DOUBLE POL...

Page 21: ...LL WIRING MINIMUM 14 AWG 250C L1 L2 G L3 1000 W 120V OR 1000 1222 W 208 230 V HEATING ELEMENT PILOT LIGHT FURNISHED INFINITE CONTROL WITH OFF POSITION TO ADDITIONAL FOOD WARMERS LINE WIRES P L1 L2 H1...

Page 22: ...3 AB0 0001 Divider bar 21 00 x 90 3234242 Plastic drain 1701273 Trim gasket sold by foot Cap Tube Chart R134A Refrigerant Model Number Cap Tube Size Length N8118B 036ID x 72 N8130B 036ID x 72 N8143B 0...

Page 23: ...pter bar 243 AB0 0001 243 AB0 0001 243 AB0 0001 243 AB0 0001 243 AB0 0001 8 Perforated pan clip 270 0V5 0030 270 0V5 0031 270 0V5 0032 270 0V5 0033 270 0V5 0034 9 Black airflow extrusion 316 991 0030...

Page 24: ...lay and overload NF5 5CLX 8 3516322 Filter dryer 2 inlet 25 9 075 231 0030 Pan condensate 10 3516454 Condenser Coil Miscellaneous Parts Not Included in Condensing Unit 2194099 15 Amp switch 120V 21944...

Page 25: ...HP Condenser Coil 2 3516554 Blade Fan 9 00 5 pedal 3 2160019 Guard Fan Condenser Upright 4 2162716 Motor Fan 16W 115V 4 2162721 Motor Fan 16W 230V 5 3516324 High Pressure Switch 6 3527001 Compressor...

Page 26: ...tand 5 031 264 0000 Bracket fan motor blower coil 6 3516172 Blade fan 5 56 CCW Lexan clear 7 2162691 Motor fan 115v 50 60 UPPCO bay 7 2162692 Motor fan 230V 50 60 UPPCO bay 8 026 ANM 0030 Fan baffle 9...

Page 27: ...3516360 Tank receiver 7 3516456 Coil condenser 3 4 HP 075 231 0031 Pan condensate 3516433 Blade fan 25 10 CW upright 2162716 Motor fan 16W 115V Condensing Unit Assembly 1 2 H P N8144 FA N8157 FA Key D...

Page 28: ...n 1 2194075 Immersion heater 120V 1Ph 1 2193974 Immersion heater 240V 1Ph 5KW 2 026 AO6 0041 Box control galv 8600 series 3 372 ANQ 003D Front collar mounting 8600 4 2193979 Switch 3 position 30Amp 5...

Page 29: ...eating 208 230v 1000 1222w 6 2194006 Element heating 120v 7 000 BQ9 Z0000 Well hot food with drain 7 000 BQ9 Z0001 Well hot food without drain 3234557 Knob infinite control 2194110 Control infinite 24...

Page 30: ...or will not be reimbursed under warranty unless pre approved with a Service Work Authorization from Delfield You must submit the number with the service claim Labor Of 1 Hour Is Allowed To Replace Com...

Page 31: ...N8000 Series Drop In Installation and Operation Manual 31 For customer service call 800 733 8829 800 733 8821 Fax 989 773 3210 www delfield com Delfield Notes...

Page 32: ...Mt Pleasant MI Covington TN 980 S Isabella Rd Mt Pleasant MI 48858 U S A 989 773 7981 or 800 733 8829 Fax 989 773 3210 www delfield com Delfield reserves the right to make changes in design or specifi...

Reviews:

Related manuals for 8100-EF