After Sales Care Support:
For the UK market only: Tel.
01491 821 821 -
email:
The installation guide is available on: www.delabie.co.uk
For all other markets: Tel.
+33 (0)3 22 60 22 74 -
email:
The installation guide is available on: www.delabie.com
NB: It is possible to adjust the temperature from 30 - 60°C by removing the control knob and turning
the notched spindle all the way in one direction or the other to achieve the desired temperature.
THERMAL & CHEMICAL SHOCKS
• PREMIX COMPACT is designed to withstand the thermal and chemical shocks recommended
within current regulations.
• To undertake a thermal shock (
fig. D
):
- Remove the covering cap
a
using a flat-headed screwdriver.
- Loosen the locking screw
b
using a Phillips screwdriver.
- Remove the control knob
c
by hand.
- Turn the notched spindle
d
¾-turn to the left.
- Shut off the cold water supply.
- Once the thermal shock is complete, do not forget to re-set the temperature to the initial setting.
- Replace the control knob
c
.
SERVICING
Check the temperature setting and the anti-scalding safety at least twice a year (depending on the water quality).
To ensure continued reliability of the PREMIX, and to conform with local Anti-Legionella legislation,
we recommend checking the following at least twice a year:
• Non-return valves, filters and replaceable cartridge: de-scale or replace worn or damaged parts.
• Mixing chamber: de-scale.
If the PREMIX is not mixing correctly (fig. E):
• Balance the pressure. The pressure differential between the hot water and the cold water must be less
than 1 bar.
• Check the hot water supply temperature. The temperature should be higher than 55°C
• Shut off the water supply.
• Check that the filters
f
have been installed correctly. Replace if necessary
• Check the non-return valves
e
. Replace if necessary.
• The water supply must be connected using nuts with a compacted flange or a flat faced tap connector.
• To remove the mechanism:
- Unscrew the outlet nipple
l
using a 33mm spanner.
- Remove the spring
k
.
- Remove the water guide
j
.
- Remove the thermostatic element and the shuttle
i
by hand.
• Clean the thermostatic element and the shuttle
i
.
• Clean the mixer body interior.
• Check the O-ring.
• Replace the mechanism. Turn on the water supply. Always carry out a cold water failsafe check after
dismantling or carrying out maintenance.
MAINTENANCE & CLEANING
•
Cleaning chrome:
do not use abrasive, chlorine or any other acid-based cleaning products.
Clean with mild soapy water using a cloth or a sponge.
•
Frost protection:
drain the pipes and operate the mixer/tap several times to drain any remaining
water. In the event of prolonged exposure to frost, we recommend taking the mechanisms apart
and storing them indoors.