DEKON D-BM100 OPTICAL BEAM 

SMOKE DETECTOR 

Doc:UM-D-BM100-0717-EN 

Page 12/16 

Fig. 6 Jumpers for detector operation declaration 

Declared sensitivity levels: 

-

 

jumper in position 50% 

low sensitivity

-

 

jumper in position 30% 

medium sensitivity

-

 

jumper in position 18% 

high sensitivity

* 50% sensitivity threshold is not LPCB approved.

Alarm mode declaration 

Jumper in W1 position 

 sustain of alarm condition 

 

after detector’s activation

, the alarm relay changes its 

position and stay unchanged as long as the power supply is on. Short brake of power supply of the detector 
will reset the detector and make the relay returned to the standard position. 

Jumper  in  W2  position 

  lack  of  sustain  of  alarm  condition 

 

after  detector’s  activation

,  the  alarm  relay 

changes its position and stay unchanged as long as detector detects fire factor. After fire factor disappeared, 
the alarm relay returns to the standard position.  

Summary of Contents for D-BM100

Page 1: ...Doc No UM D BM100 0717 EN DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Installation and maintenance manual UM D BM100 0717 EN Revision 0...

Page 2: ...Research Centre for Fire Protection CNBOP J zef w Poland an EU notified authority No 1438 confirming its compliance with the requirements of the PN EN 54 12 2005 standard Read the manual carefully bef...

Page 3: ...ed Protection against ingress of foreign bodies 4 6 Passed Monitoring of detachable detectors and connections 4 7 Passed Additional requirements for software controlled detectors 4 9 Passed Electromag...

Page 4: ...opposite wall A single casing embraces a laser pointer that enables optical path axis alignment between the detector and the reflector set of reflectors The D BM100 beam smoke detector is intended to...

Page 5: ...ipped with automatic compensation mechanism to monitor its contamination and environment impact conditions The circuits guarantee the same sensitivity level in the whole compensation range At a certai...

Page 6: ...100 m or with the D BM50 1 prism reflector operating distance is from 5 m to 50 m Set of reflectors single reflector test foil and an adjustment mirror are not included in the detector standard pack a...

Page 7: ...sting operation especially in dusty premises may result in contamination dust dirt accumulation of the optical part of the detector and of the reflector set of reflectors After exceeding a determined...

Page 8: ...and masks during detector installation works that produce high amount of dust such as hole drilling for detector base mounting on ceilings walls 7 4 Eye protection against laser beam operating equipm...

Page 9: ...beam and a side wall of room should not exceed D value and between two adjacent detector beams 2D The distance from the IR beam to any obstacle e g a wall perpendicular to a side wall shall not be sho...

Page 10: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 10 16 Fig 3 D BM100 design and overall dimensions...

Page 11: ...TOR Doc UM D BM100 0717 EN Page 11 16 Fig 4 D BM100 detector installation wires connection Fig 5 D BM100 detector internal connections and output terminals diagram Power supply Connection of detection...

Page 12: ...er in W1 position sustain of alarm condition after detector s activation the alarm relay changes its position and stay unchanged as long as the power supply is on Short brake of power supply of the de...

Page 13: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 13 16 Fig 7 D BM100 detectors connection into detection line...

Page 14: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 14 16 Fig 8 D BM50 1 prism reflector Fig 9 D BM100 4 set of reflectors...

Page 15: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 15 16 Fig 10 D BM100 detector testing foil with overprints...

Page 16: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 16 16 Fig 11 Assembly set of reflectors and the service mirror...

Reviews: