Once ENTER is pressed use UP or DOWN arrows to change value then press ENTER to save. Using
UP/DOWN arrows repeat for Vac CutOut and save again by pressing ENTER
NOTE: When set up for multimachine, controller must be in STOPPED mode when changing Setpoints.
Multimachine Setup
Multimachine allows two or more Controllers to communicate and rotate Lead and Lag pumps based on
hours Run. When rotation occurs the pump with the least hours will rotate to Lead if the hours are
imbalanced. This keeps from putting all the run hours on one pump. To set up for multimachine CAT5
Ethernet cables are run from the RS485 jack mounted inside the panel. The cable is plugged into the jack
in the first panel, then routed to the second panel and plugged in. Each panel has two jacks so that you
can run cables to each machine if more than two. Cables must be run before setting the Controller up
for multimachine. Once cables are run go to first Controller and Enter Password.
Now press PROG button twice to view System Options Screen
Press DOWN arrow until Multimachine is selected.
Press ENTER.
Even though multimachine may already be set for 1 use UP button to move to 2 then back to 1
DOWN
ENTER
UP