2.2 Software
2.2.1 Downloading and installing PICUS
See the
PICUS manual
for how to download and install PICUS.
INFO
PICUS automatically detects any controller that is connected to the same network. No additional configuration is
required.
2.3 Information
2.3.1 System drawings
The following must be available:
Drawing
Used to
Detailed drawings
Configure the inputs and outputs in PICUS
2.3.2 AC protections
To avoid delays during commissioning, ensure that the list of protections for each controller is available.
2.3.3 Transformer information
To avoid delays during commissioning, ensure that configuration information is available for each current transformer, voltage
transformer and step-up transformer in the system.
2.3.4 Breaker information
To avoid delays during commissioning, ensure that the manufacturer's information is available for each breaker that the
controllers will control. This information should include:
• The breaker type.
• Breaker characteristics, especially the breaker closing time. Other breaker characteristics are also useful, like the spring
loading time for a compact breaker.
2.3.5 Input/output and parameter configuration
The following information must be available:
GPU 300 Commissioning guidelines 4189341033 UK