DM-4 Land/DM-4 Marine
4189340465C
Replacement Instructions, AOP-2
DEIF A/S
Page 3 of 4
1. Replacement of the Additional Operator Panel 2 (AOP-2)
General instruction
Before replacing any modules, please refer to the General Instruction for replacement of Delomatic
4 modules.
Please do not switch over modules from one DGU to another before consulting the
documentation provided by DEIF A/S, and preferably consulting DEIF A/S.
Please let us know if you do switch modules permanently, this will help us keep our records
updated. Call us or send a fax to DEIF A/S, for the attention of the service department:
Tel.: + 45 9614 9614
Fax: +45 9614 9615
When modules are replaced due to updating or due to any malfunctions, please let us know
the exact location of new modules.
Replacement of module
- Switch all equipment into switchboard control
- Remove the power supply from the defective DGU
- Remove other connections/plugs on the AOP-2
- Take out the text labels from the defective AOP-2 and insert these into the pockets on the
new AOP-2
- Connect the plugs and power supply again
- Set the CAN slave ID according to the correct configuration, please see the HMI setup
document
- Make a test to secure that the system works as predetermined
A
p
p
./B
oo
tl.
En
d
Re
s
.
Be aware of static electricity when handling!