Page 2 of 8
Tel.: (+45) 9614 9614
•
Fax: (+45) 9614 9615
•
E-mail: [email protected]
General data
Input voltage:
3 x 400/480V AC ±15%
Type: DCP2-2420 and DCP2-2440
1 x 230V AC ±15%
Type: DCP2-1210, DCP2-2410 and
DCP2-2420
1 x 115V AC ±15%
Type: DCP2-2410/115V
1 x 230V AC ±15%
Type: DCP2-1205 and DCP2-2405
Output voltage:
23.5-27.5V DC (type DCP2-24XX and -2410/115V)
11.8-13.8V DC (type DCP2-12XX)
Output current:
DCP2-XX05:
5A (typical current limit 6A)
DCP2-XX10 and -2410/115V:
10A (typical current limit 12.5A)
DCP2-2420:
20A (typical current limit 25A)
DCP2-2440:
40A (typical current limit 45A)
Terminals:
DCP2-1205, -1210, -2405, -2410 and -2410/115V:
Primary max.
2.5 mm²
Secondary
2.5 mm²
DCP2-2420:
Primary max.
2.5 mm²
Secondary
4.0 mm²
DCP2-2440:
Primary max.
2.5 mm²
Secondary
10.0 mm²
Indication:
Green LED – operating indication
Housing:
Materials:
All plastic parts are self-extinguishing to UL94 (V0)
DCP2-2440 is encapsulated in a metal housing
Dimensions:
147 x 123 x 86 mm (DCP2-1205, -2405)
L x W x H
205 x 123 x 86 mm (DCP2-1210, -2410, -2410/115V)
(Appendix)
240 x 153 x 86 mm (DCP2-2420)
292 x 185 x 130 mm (DCP2-2440)
Distance for con-
vection:
100 mm above and below the DCP2, 30 mm to each side
Mounting:
DIN-rail, EN 50022-35