Table 4.5
Plug 5: Digital input
Terminal Text
Function
Technical data
39
In
Configurable
Negative switching only, < 100 Ω
40
In
Configurable
Negative switching only, < 100 Ω
41
In
Configurable
Negative switching only, < 100 Ω
42
In
Configurable
Negative switching only, < 100 Ω
43
In
Configurable
Negative switching only, < 100 Ω
44
In
Configurable
Negative switching only, < 100 Ω
45
In
Configurable
Negative switching only, < 100 Ω
46
In
Configurable
Negative switching only, < 100 Ω
47
MB on
Configurable (application dependent) Negative switching only, < 100 Ω
48
MB off
Configurable (application dependent) Negative switching only, < 100 Ω
49
GB/TB on
Configurable (application dependent),
also used for BTB ON
Negative switching only, < 100 Ω
50
GB/TB off
Configurable (application dependent),
also used for BTB OFF
Negative switching only, < 100 Ω
Table 4.6
Plug 6: Analogue output
Terminal Text
Function
Technical data
51
GOV (-)
Voltage or PWM output
Isolated
52
GOV (+)
Voltage or PWM output
Isolated
53
Not used
-
-
54
AVR (-)
Voltage output
Isolated
55
AVR (+)
Voltage output
Isolated
Table 4.7
Plug 7: AC current CT-side
Terminal Text
Function
Technical data
56
L1 (S1)
57
L2 (S1)
58
L3 (S1)
59
Com (S2)
Common
Must be connected to frame GND
60
L4 (S1)
Neutral, Earth or Mains/Tie power
61
L4 (S2)
Neutral, Earth or Mains/Tie power
Must be connected to frame GND
Table 4.8
Plug 8: AC voltage measurement
Terminal Text
Function
Technical data
62
N
A-side
63
L1
A-side
64
L2
A-side
65
L3
A-side
INSTALLATION INSTRUCTIONS UK
Page 11 of 22