4. Status line text
4.1 Status line text
4.1.1 Standard texts
Condition
Comment
BLOCK
Block mode is activated
SIMPLE TEST
Test mode is activated
FULL TEST
SIMPLE TEST ###.#min
Test mode activated and test timer counting down
FULL TEST ###.#min
ISLAND MAN
Genset stopped or running and no other action taking
place
READY ISLAND AUTO
Genset stopped in Auto
ISLAND ACTIVE
Genset running in Auto
AMF MAN
Genset stopped or running and no other action taking
place
READY AMF AUTO
Genset stopped in Auto
AMF ACTIVE
Genset running in Auto
LOAD TAKEOVER MAN
Genset stopped or running and no other action taking
place
READY LTO AUTO
Genset stopped in Auto
LTO ACTIVE
Genset running in Auto
DG BLOCKED FOR
START
Generator stopped and active alarm(s) on the genera-
tor
GB ON BLOCKED
Generator running, GB open and an active "Trip GB"
alarm
SHUTDOWN OVERRIDE The configurable input is active
ACCESS LOCK
The configurable input is activated, and the operator
tries to activate one of the blocked keys
GB TRIP EXTERNALLY
Some external equipment has tripped the breaker
An external trip is log-
ged in the event log
MB TRIP EXTERNALLY
Some external equipment has tripped the breaker
An external trip is log-
ged in the event log
IDLE RUN
The "Idle run" function is active. The genset will not
stop until a timer has expired
IDLE RUN ###.#min
The timer in the "Idle run"’ function is active
Aux. test ##.#V ####s
Battery test activated
START PREPARE
The start prepare relay is activated
START RELAY ON
The start relay is activated
CGC 400 Operator's manual 4189340787