![DEGA 40100002 Instruction Manual Download Page 14](http://html.mh-extra.com/html/dega/40100002/40100002_instruction-manual_2464854014.webp)
14
Add-on modules
Product code
Name
Product description
40200010
DEGA NS III RS485
Internal output RS485
40200011
DEGA NS III Buzzer
Internal buzzer on PCB, 4 VDC, 7 VDC, 30mA, 88 dB
Attachments
1.
Chart for setting the transmitter adress
adress
1
2
3
4
5
1
ON
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
4
OFF
OFF
ON
OFF
OFF
5
ON
OFF
ON
OFF
OFF
6
OFF
ON
ON
OFF
OFF
7
ON
ON
ON
OFF
OFF
8
OFF
OFF
OFF
ON
OFF
9
ON
OFF
OFF
ON
OFF
10
OFF
ON
OFF
ON
OFF
11
ON
ON
OFF
ON
OFF
12
OFF
OFF
ON
ON
OFF
13
ON
OFF
ON
ON
OFF
14
OFF
ON
ON
ON
OFF
15
ON
ON
ON
ON
OFF
adress
1
2
3
4
5
16
OFF
OFF
OFF
OFF
ON
17
ON
OFF
OFF
OFF
ON
18
OFF
ON
OFF
OFF
ON
19
ON
ON
OFF
OFF
ON
20
OFF
OFF
ON
OFF
ON
21
ON
OFF
ON
OFF
ON
22
OFF
ON
ON
OFF
ON
23
ON
ON
ON
OFF
ON
24
OFF
OFF
OFF
ON
ON
25
ON
OFF
OFF
ON
ON
26
OFF
ON
OFF
ON
ON
27
ON
ON
OFF
ON
ON
28
OFF
OFF
ON
ON
ON
29
ON
OFF
ON
ON
ON
30
OFF
ON
ON
ON
ON
31
ON
ON
ON
ON
ON
2.
Signalization transmitted by the current loop 4-20 mA
Measurement:
The measure concentration is directly proportional to 4-20 mA current output
Exceeding the range of measured concentrations:
Current output ranges from 20-22 mA
End of valid calibration:
Current output transmits the actual measured concentration for 9 s in a 4-20 mA range and
for 1 s 2 mA current
Malfunction:
Current output will be set to 0,5 mA
Mainternace:
Current output will be set to 1 mA
3.
Conversion between volume concentration and lower explosive limit of methane
% DMV
– concentration level of the lower explosive limit in %
% obj
– gas volume sample
4,4
– lower explosive limit of methane (4.4% vol.)
4.
Package contents
1 x transmitter
1 x bushing