Define Instruments TEX-BAR Manual Download Page 20

TEX-BAR-MAN-15V05 (0903)

Copyright © 2015 Defi ne Instruments

20

ABOVE

: Relay turns on above the setpoint value and off  below it. 

BELW

: Relay turns on below 

the setpoint value and off  above it.

 _ _ _ SETPOINT TYPE

 scrolls across the display and toggles with the current 

selection. Using the 

 and 

 buttons, select either 

ALRM

 (alarm) or 

CNTRL

 

(control), and then press 

ALRM - SETPOINT VALUE

 controls setpoint 

activation point. 

HYSTERESIS VALUE

 con-

trols setpoint deactivation point.

CNTRL - SETPOINT VALUE

 controls setpoint 

deactivation point. 

HYSTERESIS VALUE 

con-

trols setpoint reactivation point.

Energised Above

Hysteresis
band

Energised Below

Hysteresis
band

Energised Above

Hysteresis
band

Energised Below

Hysteresis
band

_ _ _ HYSTERESIS VALUE

 scrolls across the display and toggles with the hyster-

esis value for the selected setpoint. Use the 

 and 

 buttons to adjust this 

value if required, and then press 

.

The 

HYSTERESIS VALUE

 

defi nes the separation band between setpoint activation and deacti-

vation, and will operate as per the 

SETPOINT TYPE

 setting selected in 7.2D.

 _ _ _ MAKE DELAY 

scrolls across the display and toggles with the current make 

delay time for the selected setpoint. This is the time delay between setpoint ac-

tivation, and when the relay turns on. Adjust this value in 0.1 second increments 

using the 

 and 

 buttons, and then press 

.

 _ _ _ OPEN ACCESS TO SP VALUE

 scrolls across the display and toggles with the 

open access permission setting for the selected setpoint. Use the 

 and 

 to 

select either 

NO

 or 

YES

, and then press 

.

When enabled, this option allows the selected setpoint's value to be edited directly aft er press-
ing the 

 button, without needing to enter a PIN number or go through all of the other op-

tions. Each setpoint can individually have this option enabled or disabled. See Section 8.

The step that you proceed to now will depend on which setpoint you are editing 

(selected in 7.2A):

 

If you are currently editing 

SP 1

, skip to 7.2J now.

 

If you are currently editing 

SP 2–4

, continue to 7.2I now.

Summary of Contents for TEX-BAR

Page 1: ...LC and monitoring systems TEX BAR 4 20mA 0 10V Bar Graph Order Codes TEX BAR Processcontroller Bargraph HV LV 85 265V AC 95 370V DC 15 48V AC 10 72V DC Options R2 R4 2 x relay outputs 4 x relay output...

Page 2: ...10V Comm Port Number of comm ports None or 1 Comm port options S2R Isolated RS232 RJ terminal or S4S Isolated RS485 screw terminal Programming Buttons Up Down Prog P buttons Factory calibrated for all...

Page 3: ...to save your settings and advance to the next step in the setup process The Down button is used to access the Setpoint Setup menu Section 7 and the Setpoint Open Access menu Section 8 It is also used...

Page 4: ...racters The 5 digit 7 segment display is chiefly intended for displaying numbers However when navigating the setup menus alphabetic characters will also be displayed This table is provided for your re...

Page 5: ...e 3 6 3 1C Power Supply HV LV See 3 7 3 1D Relay Output See 3 3 3 1E Serial Port See 3 5 3 1F Analog Output See 3 4 A D B C E F 3 2 Wire the analog input See 3 1A Wire the analog input as required for...

Page 6: ...pplied excitation 3 3 Wire the relay outputs if installed See 3 1D If your controller has relay outputs installed wire them as shown below Relays can be programmed to operate within the total span ran...

Page 7: ...is activated Hold Holds the current display value Test Resets the meter Test Hold COM NC NC 3 7 Wire the power supply See 3 1C Wire your controller for either low or high voltage power supply as show...

Page 8: ...IONS INSTALLATION 4 1 Case dimensions Cabling Allowance 48mm 1 89 45mm 1 77 120mm 4 72 39mm 1 54 155mm 6 10 minimum depth required behind panel 4mm 0 16 Cabling Allowance 96mm 3 78 92mm 3 62 120mm 4 7...

Page 9: ...meter body and pro truding cabling B Remove the Mounting Clips from the meter back C Slide the Panel Gasket over the rear of the unit to the back of the Meter Faceplate D From the front of the panel i...

Page 10: ...t posi tion of 20mA suitable for 0 20mA and 4 20mA inputs You will need to shift the input header if You are using the 0 2V or 0 10V input range or You are changing your input type or range from a pre...

Page 11: ...Mode in software from the front panel see 6 2C G Slide the input module back into the meter case Make sure that it is sitting in the tracks on the left and right Press firmly until the input module is...

Page 12: ...ls across the display and toggles with SKIP Press to skip to 6 3 or the button and then to ENTER input setup B _ _ _ MAINS FREQUENCY scrolls across the display Use the and buttons to select 50HZ or 60...

Page 13: ...e uses low and high display values and is intended for a pre calibrated sensor with a known output range For example 4mA 0 and 20mA 1000 It does not require any input signals to be applied to the cont...

Page 14: ...ed in 6 2C 0MA for 0 20mA 4MA for 4 20mA or 0V for 0 2V 0 10V F _ _ _ ENTER DISPLAY VALUE FOR HIGH MA V scrolls across the display and toggles with the current high display value Use the and buttons t...

Page 15: ...es will stabilise measurement but it will also slow down re sponse rates A typical value is 4 C _ _ _ AVE WINDOW scrolls across the display and toggles with the currently selected averaging window val...

Page 16: ...ect a mA or volt meter across the analog output connector see 3 4 and then continue to 6 5E If you selected Skip skip to 6 6 now E _ _ _ CAL LOW ANALOG OUTPUT scrolls across and toggles with a calibra...

Page 17: ...n a system It applies particularly to MODBUS mode when used on an RS485 serial network The serial address of the controller must be set to match the serial address defined in the master device Refer t...

Page 18: ...ay and toggles with SKIP Press to skip and return to the operational display or the button and then to ENTER and change your PIN number B _ _ _ ENTER NEW CAL PIN NUMBER scrolls across the display and...

Page 19: ...PIN is entered setup is started at 7 2 If an incorrect PIN number is entered _ _ _ INCORRECT PIN NUMBER ACCESS DENIED scrolls across the display and it returns to normal operating mode You will have...

Page 20: ...RESIS VALUE defines the separation band between setpoint activation and deacti vation and will operate as per the SETPOINT TYPE setting selected in 7 2D F _ _ _ MAKE DELAY scrolls across the display a...

Page 21: ...ingle bar Multiple setpoints may have this option enabled Use the and buttons to select NO or YES and then press K _ _ _ EDIT SETPOINT scrolls across the display and toggles with SKIP You are now back...

Page 22: ...he last ena bled setpoint will exit and return to the operational display 9 RESET PIN NUMBERS VIEW FIRMWARE VERSION If you have forgotten your PIN number s follow the procedure below to reset both the...

Page 23: ...ed data which includes decimals and any text characters that may be selected to show units However it is also possible to read un formatted data by using a U in the read command There is no unformatte...

Page 24: ...Signed Address Function 2 Process display 12 Peak 13 Valley 6 9 Setpoint 1 4 SP1 6 SP2 7 SP3 8 SP4 9 34 D A scale low value 36 D A scale high value Custom ASCII Registers Controller Response After the...

Page 25: ...ster addresses are displayed in the Modicon 5 digit addressing format I e Register 65 40065 subtract 1 for direct addressing A 3 Ranger A mode Ranger A is a continuous output used to drive remote disp...

Page 26: ...TEX BAR MAN 15V05 0903 Copyright 2015 Define Instruments 26...

Page 27: ...TEX BAR MAN 15V05 0903 Copyright 2015 Define Instruments 27...

Page 28: ...835 1550 Aus 1800 810 820 Fax 64 9 835 1250 sales defineinstruments co nz www defineinstruments co nz United States Dallas TX Ph 214 926 4950 sales defineinstruments com www defineinstruments com Sout...

Reviews: