SETPOINT SETUP
The soft ware in your controller will allow you to confi gure up to 4 setpoints,
however full functionality is only supported when relay output hardware installed.
(Setpoints with no corresponding relay output hardware may be used as simple LED
indicators, if desired. In this case, features requiring relay output functionality will
continue to appear in the setup menu, but will be ignored by the controller.)
7.1 - Enter SP PIN number
A
Enter setpoint setup mode by pressing and holding the
button for 3 seconds.
_ _ _ ENTER SP PIN NUMBER
scrolls across the display and toggles with
0
. Use
the
and
buttons to enter your security code (factory default 1). Then
press
. If the correct PIN is entered, setup is started at 7.2.
If an incorrect PIN number is entered,
_ _ _ INCORRECT PIN NUMBER – ACCESS
DENIED
scrolls across the display, and it returns to normal operating mode.
You will have the opportunity to change your PIN number at the end of this section
(7.3). If you have forgotten your PIN number, see Section 9.
7.2 - Setpoint setup
A
_ _ _ EDIT SETPOINT
scrolls across the display and toggles with
SKIP
. Press
now to skip to 7.3, or use the
and
buttons to select a setpoint to edit,
and then press
.
B
_ _ _ SP VALUE
scrolls across the display and toggles with the current value for
the selected setpoint. Using the
and
buttons, adjust the display value at
which the selected setpoint will activate, and then press
.
C
_ _ _ SP ACTIVATION
scrolls across the display and toggles with the activation
for the selected setpoint. Using the
and
buttons, select the relay activa-
tion to operate
ABOVE
or
BELW
(below) the setpoint value, and then press
.