- 4 -
4. CONDENSED OPERATION INSTRUCTONS
OPERATION:
The CO detector is operational once
the activation switch is slid to
ON
position. If the
detector’s power is active, the
POWER
green LED
will flash once every 60 seconds, and the LCD
readout will continuously display ON, or the current
CO level if 30 PPM or more is detected.
ALARM CONDITION:
When the batteries are active, and CO gas is detected at a level
and duration specified in Section 3 of the Owner’s Manual, the horn will sound and
ALARM
red LED will light. The alarm signal will sound 4 short beeps every 6 seconds,
and flash the
ALARM
red LED in sync with the beeping sound. The LCD will also display
the current CO level detected. After having alarmed for more than 5 minutes, the alarm
signal will change to 4 short beeps every 60 seconds. The alarm signal is either
manually or automatically reset. See Section 10 of Owner’s Manual
WHAT TO DO WHEN
THE ALARM SOUNDS
.
Beeps 4 times every 6 seconds
for first 5 minutes
Beeps 4 times per minute
after 5 minutes
TEST/RESET/MUTE
BUTTON:
The
TEST/RESET/MUTE
button is used to check
the detector for proper operation, and to
temporarily mute horn for 5 minutes when alarm
is activated, for 24 hours during the first week of
a “Low Battery Voltage” signal (
)
activation, or
for 60 hours during the first month of a sensor
“End-of-Life” signal (
) activation. The LCD
will display the current CO level detected when detector is being tested, or
when
an alarm signal is muted. See Section 9 of Owner’s Manual
TEST AND MUTE
DETECTOR
for detailed instructions to test the detector and mute the audible horn.