background image

 

- 3 - 

 

3.  INSTALLATION INSTRUCTIONS 

 
Follow these steps in this order to install the CO detector: 

1.  Fasten the mounting plate to the wall at eye 

level, about 5’ off the floor. 

 

Slide detector down onto mounting plate. 

 

Connection between mounting plate and 
detector will automatically turn activation switch 

ON

 

2.  Press and hold test button until detector 

starts to beep, then release. The detector 
should beep 4 times, pause, and then 
beep 4 times again. 

ALARM

 red LED 

should flash at the same time. 

 

3.  Secure detector to mounting plate, with Phillips 

head screw provided, through the mounting hole 
on top of detector. 

 

 

Summary of Contents for CD8180

Page 1: ...cial Carbon Monoxide Detector is Underwriters Laboratories Listed to ANSI UL 2075 and designed to help measure compliance with the U S Occupational Safety and Health Administration OSHA workplace exposure limits The CD8180 does not comply with ACGIH Cal OSHA or NIOSH which recommend lower exposure limits than OSHA Consult with your local authority about the exposure limits permitted for your workp...

Page 2: ...y maintenance room that contains combustion equipment such that an alarm signal will be heard before anyone enters the building or maintenance room For residential areas within a commercial building carbon monoxide alarms that are listed to the UL 2034 residential standard like the Defender CA6150 should be installed inside or near every sleeping area or room according to the manufacturer s instru...

Page 3: ...ng plate Connection between mounting plate and detector will automatically turn activation switch ON 2 Press and hold test button until detector starts to beep then release The detector should beep 4 times pause and then beep 4 times again ALARM red LED should flash at the same time 3 Secure detector to mounting plate with Phillips head screw provided through the mounting hole on top of detector ...

Page 4: ...having alarmed for more than 5 minutes the alarm signal will change to 4 short beeps every 60 seconds The alarm signal is either manually or automatically reset See Section 10 of Owner s Manual WHAT TO DO WHEN THE ALARM SOUNDS Beeps 4 times every 6 seconds for first 5 minutes Beeps 4 times per minute after 5 minutes TEST RESET MUTE BUTTON The TEST RESET MUTE button is used to check the detector fo...

Page 5: ...total length of time the highest CO level was detected within 10 of the peak from 1 to 999 minutes Current CO Level e g 10 PPM detected within last minute Highest CO Level e g peak of 25 PPM detected within last 30 days Duration of Peak CO Level e g peak detected for 60 minutes Each reading will appear for five seconds To erase the record in memory press the Display CO Level button and while the r...

Reviews: