Tab.3
Flue gas outlet dimensions
Output (P)kW
(80/60° C)
Number of boil
ers
dia. D (mm)
H = 0 - 2 m
H = 2 - 5 m
H = 5 - 9 m
H = 9 - 13 m
H = 13 - 17 m
294
2
180
185
190
195
200
441
3
215
220
225
235
235
588
4
260
265
270
275
275
735
5
300
300
305
310
315
882
6
330
335
340
340
345
1029
7
360
365
370
370
370
1176
8
390
390
395
400
400
5.3.6
Material
Warning
The coupling and connection methods may vary depending on
the manufacturer. It is not permitted to combine pipes, coupling
and connection methods from different manufacturers.
The materials used must comply with the prevailing regulations
and standards.
Tab.4
Flue gas outlet pipework materials
Material
Single-wall, rigid
Thick-walled, aluminium
Plastic T120
Stainless steel
Flexible
Plastic T120
Stainless steel
(1) The sealing must conform to pressure class 1
(2) With CE marking
Tab.5
Air supply pipework materials
Version
Material
Single-wall, rigid
Aluminium
Plastic
Stainless steel
Flexible
Aluminium
Plastic
Stainless steel
5.3.7
Additional guidelines
For installing the flue gas outlet and air supply materials, refer to the in
structions of the manufacturer of the relevant material. If the flue gas
outlet and air supply materials are not installed in accordance with the
instructions (e.g. not leakproof, not correctly bracketed), this can result
in dangerous situations and/or physical injury. After installation, check at
least all flue gas outlet and air supply parts for tightness.
Direct connection of the flue gas outlet to structural ducts is not permit
ted because of condensation.
Always clean shafts thoroughly when using lining pipes and/or an air
supply connection.
5 Installation
7680446 - v.01 - 14082017
MCA
41