Room-ventilated, high pressure
Sizes of the flue gas outlet/air supply connections: room-ventilated, high
pressure
Connection sizes for MCA 160: ∅ 150/150 mm
Instructions for using the table:
look for the desired output P (in kW at 80/60° C) in the left column.
Then take the available height (H) from the right columns.
If necessary, round up the diameter found to the available size sold.
Important
The boiler's parameter settings will need to be changed. Contact
us for more information.
Tab.2
Flue gas outlet dimensions
Output (P)kW
(80/60 °C)
Number of boilers dia. D (mm)
H = 0 - 2 m
H = 2 - 5 m
H = 5 - 9 m
H = 9 - 13 m
H = 13 - 17 m
294
2
150
150
160
165
170
441
3
185
190
195
200
205
588
4
225
225
235
235
240
735
5
250
255
260
265
270
882
6
280
285
290
295
295
1029
7
305
305
310
315
320
1176
8
325
330
335
335
340
Room-sealed version, high pressure
Sizes of the flue gas outlet/air supply connections: room-sealed version,
high pressure
Connection sizes for MCA 160: dia. 150/150 mm
Instructions for using the table:
look for the desired output P (in kW at 80/60° C) in the left column.
Then take the available height (H) from the right columns.
If necessary, round up the diameter found to the available size sold.
Important
The boiler's parameter settings will need to be changed. Contact
us for more information.
Fig.36
Room-ventilated version
AD-0000862-01
D
D
H
Fig.37
Room-ventilated version
AD-0000863-01
D
D
D
D
D
D
H
5 Installation