![DeDietrich GT 530-10 Installation And Service Manual Download Page 11](http://html1.mh-extra.com/html/dedietrich/gt-530-10/gt-530-10_installation-and-service-manual_2462454011.webp)
11
25/01/2012 - 300011906-001-D
GT 530
3.3.2
Boilers for following countries: Germany, Austria, Serbia, Slovenia
Conditions of use:
Maximum operating pressure: 6 bar
Maximum operating temperature: 100 °C
Maximum operating temperature: 120 °C
(in accordance with TRD 702)
Boiler thermostat setting: 30 to 90°C
Safety thermostat setting: 110 °C
*Maintenance consumption: total heat emission when the burner is
off as a percentage of the nominal input power when the difference
between the mean boiler temperature and the room temperature is
30 K - in accordance with DIN 4702 - EN303.
Boiler
GT
530
-9
GT
530
-10
GT
530
-11
GT
530
-12
GT
530
-13
GT
530
-14
GT
530
-15
GT
530
-16
GT
530
-17
GT
530
-18
GT
530
-19
GT
530
-20
GT
530
-21
GT
530
-522
GT
530
-23
GT
530
-24
GT
530
-525
Useful output
kW
415
to
460
460
to
505
505
to
550
550
to
595
595
to
640
640
to
685
685
to
730
730
to
775
730
to
820
820
to
865
865
to
910
910
to
955
955
to
1000
1000
to
1045
1045
to
1090
1090
to
1135
1135
to
1180
Power input
kW
448
to
500
494
to
546
547
to
599
597
to
649
643
to
696
689
to
741
743
to
797
790
to
842
790
to
892
886
to
938
935
to
987
982
to
1034
1034
to
1085
1082
to
1133
1131
to
1182
1180t
o
1231
1227
to
1278
Number of sections
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Water content
l
465
503
541
579
617
655
693
731
769
807
845
905
943
981
1019
1057
1095
Water
resistance
(1)
∆
T = 10K
mbar
22
25.9
30.5
37
43.5
50
55.8
21.8
24.2
26.8
30
33
35.6
38.9
42.9
45.6
48.9
∆
T = 15K
9.8
11.5
13.6
16.4
19.3
22.2
24.8
9.7
10.8
11.9
13.3
14.7
15.8
17.3
19.1
20.3
21.9
∆
T = 20K
5.5
6.9
8.1
9.2
10.6
12
13.9
4.5
5.8
6.5
7.2
7.9
8.6
9.4
1.6
11.8
12.4
Pressure in the furnace for
nozzle pressure = 0
(4)
mbar
1.4
1.45
1.5
1.55
1.6
1.65
1.7
1.75
1.8
1.85
1.95
2.05
2.1
2.15
2.2
2.25
2.3
Flue gas temperature -
Ambient temperature
(1) (3)
K
<190
<190
<190
<190
<190
<190
<190
<190
<190
<190
<190
<190
<190
<190
<190
<190
<190
Mass flue gas
flow rate
(1) (2)
Fuel oil
Kg/h
770
850
920
1000
1070
1150
1220
1300
1370
1450
1520
1600
1670
1750
1820
1900
1970
Gas
810
890
970
1040
1120
1200
1280
1360
1440
1520
1590
1670
1750
1830
1910
1990
2070
Combustion
chamber
Inscribed
diameter
mm
614
614
614
614
614
614
614
614
614
614
614
614
614
614
614
614
614
Equivalent
diameter
mm
694
694
694
694
694
694
694
694
694
694
694
694
694
694
694
694
694
Depth
mm
928
1039
1150
1261
1372
1483
1594
1705
1816
1927
2038
2189
2300
2411
2522
2633
2744
Volume
m
3
0.36
0.40
0.45
0.49
0.53
0.57
0.61
0.65
0.70
0.74
0.78
0.84
0.88
0.92
0.96
1.00
1.05
Maintenance
consumption*
∆
T = 30K
%
0.16
0.15
0.14
0.13
0.13
0.12
0.12
0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.11
0.10
0.10
Weight (empty)
kg
2205
2391
2567
2771
2945
3120
3314
3494
3684
3872
4040
4266
4444
4639
4817
4994
5168
(1)
Nominal operation (top boiler power)
(2)
CO
2
= 13.1 to 13.5% with fuel oil and 9.5% with natural gas.
(3)
Boiler temperature: 80 °C
Ambient temperature: 20 °C
(4)
In order for the boiler to operate correctly, it is
imperative to respect the draught at the nozzle.
Summary of Contents for GT 530-10
Page 1: ...GT 530 Fuel oil gas boilers Installation and Service Manual 300011906 001 D EN ...
Page 30: ...30 GT 530 25 01 2012 300011906 001 D Insulation 71 70 M000050 ...
Page 31: ...31 25 01 2012 300011906 001 D GT 530 Casing ...
Page 37: ...37 25 01 2012 300011906 001 D GT 530 ...
Page 38: ...38 GT 530 25 01 2012 300011906 001 D ...