5.5

Modifying the user settings

5.5.1.

Setting the set point temperatures

To set the various heating, DHW and swimming pool temperatures,

proceed as follows:
1. Press the 

C

 key.

2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button.

To go back to the previous display, press the key 

j

.

4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.

To cancel, press key 

h

.

C

 Menu

Parameter

Adjustment range Description

Factory setting

DAY TEMP.A

5 to 30 °C

Desired room temperature in comfort periods on circuit A

20 °C

NIGHT TEMP.A

5 to 30 °C

Desired room temperature in reduced periods on circuit A

16 °C

DAY TEMP.B

 

(1)

5 to 30 °C

Desired room temperature in comfort periods on circuit B

20 °C

NIGHT TEMP.B

 

(1)

5 to 30 °C

Desired room temperature in reduced periods on circuit B

16 °C

DAY TEMP.C

 

(1)

5 to 30 °C

Desired room temperature in comfort periods on circuit C

20 °C

NIGHT TEMP.C

 

(1)

5 to 30 °C

Desired room temperature in reduced periods on circuit C

16 °C

DHW TEMP.

 

(1)

10 to 80 °C

Desired domestic hot water temperature in the DHW circuit

55 °C

WATER T.NIGHT

(1)

(2)

10 to 80 °C

Set tank temperature, night programme

10 °C

TEMP.TANK AUX

 

(1)

10 to 80 °C

Desired domestic hot water temperature in the auxiliary circuit 55 °C

AUX.TANK
T.NIGHT

(1)(2)

10 to 80 °C

Set tank temperature, night programme

10 °C

DHW A TEMP.

 

(1)

10 to 80 °C

Desired domestic hot water temperature in circuit A

55 °C

A.TANK T.NIGHT

(1)

(2)

10 to 80 °C

Set tank temperature, night programme

10 °C

SWIMMING P.T.B

 

(1)

5 to 39 °C

Desired temperature for swimming pool B

20 °C

SWIMMING P.T.C

 

(1)

5 to 39 °C

Desired temperature for swimming pool C

20 °C

(1) The parameter is only displayed for the options, circuits or sensors actually connected.

(2) The parameter is only displayed if 

INSTALLATION

 parameter is set to 

EXTENDED

MODE

C002266-A

Diematic iSystem For C 330 / C 630 ECO

5. Commissioning

31082018 - 7600691-001-06

42

Summary of Contents for Diematic iSystem

Page 1: ...Ireland EN Regulation Diematic iSystem For C 330 C 630 ECO C002695 A Installation User and Service Manual 7600691 001 06...

Page 2: ...Choice of the location 10 4 2 2 Connecting the outside sensor 10 4 3 Fitting and connecting the control panel 11 4 4 Electrical connections 11 4 4 1 Connecting a direct heating circuit 11 4 4 2 Connec...

Page 3: ...nd lighting on the display 44 5 5 5 Setting the time and date 45 5 5 6 Selecting a timer programme 45 5 5 7 Customising a timer programme 46 5 5 8 Setting an annual clock 48 5 6 Modifying the installe...

Page 4: ...7 5 Failure history 80 7 6 Parameter and input output check mode tests 80 7 6 1 Control system sequence 83 3 31082018 7600691 001 06...

Page 5: ...rous situation causing slight physical injury CAUTION Risk of material damage Signals important information Signals a referral to other instructions or other pages in the instructions 1 2 Abbreviation...

Page 6: ...liance with the prevailing legislation and standards 4 Perform the initial start up and carry out any checks necessary 4 Explain the installation to the user 4 If a maintenance is necessary warn the u...

Page 7: ...hat children do not play with the appliance If the mains power lead is damaged it must be replaced by the original manufacturer the manufacturer s dealer or another competent person to prevent hazardo...

Page 8: ...heating equipment must be carried out by a qualified engineer For a proper operating of the boiler follow carefully the instructions Keep this document close to the place where the boiler is installe...

Page 9: ...1149 984 842 720 616 528 454 Specifications of the flow sensor circuit B C Specifications of the DHW sensor Specifications of the system sensor Temperature in C 0 10 20 25 30 40 50 60 70 80 90 Resist...

Page 10: ...ions Description package RX12 cable AD134 TELCOM 2 voice remote monitoring module AD152 Flow sensor AD199 DHW sensor AD212 Optional PCB for 3 way valve AD249 Hot water storage tank sensor AD250 Outsid...

Page 11: ...eteorological variations 4 protected from direct sunlight 4 easy to access A Recommended position B Possible position H Inhabited height controlled by the sensor Z Inhabited area controlled by the sen...

Page 12: ...cal connections 4 4 1 Connecting a direct heating circuit L000158 D 2 4 3 On off OT BL RL 1 TS B A B 0 10V S AMB C 4 3 2 1 2 1 S AMB B 2 1 S AMB A 2 1 S SYST TA S ECS S EXT S DEP C 2 1 2 1 2 1 2 1 2 1...

Page 13: ...3 2 1 2 1 S AMB B 2 1 S AMB A 2 1 S SYST TA S ECS S EXT S DEP C 2 1 2 1 2 1 2 1 2 1 S DEP B 2 1 SCU PCU TS C AUX C On off OT BL RL PUMP A Do not connect anything to the terminal block Z Domestic load...

Page 14: ...o the PUMP connector on the PCU Settings to be made for this type of installation Parameters Access Settings to be made See INSTALLATION Installer level SYSTEM Menu EXTENDED Displaying the parameters...

Page 15: ...Connect a safety thermostat if the heating circuit is for underfloor heating 4 Remove the bridge 4 Connect the wires from the safety thermostat to the connector E Connecting an additional circuit to t...

Page 16: ...put the simulation connector in place delivered with the DHW sensor package AD212 Y Connect the outside temperature sensor U Connect the heating pump circuit B I Connect the 3 way valve circuit B O Do...

Page 17: ...minal block Z Connect a safety thermostat if the heating circuit is for underfloor heating 4 Remove the bridge 4 Connect the wires from the safety thermostat to the connector E Connecting an additiona...

Page 18: ...connection P Connect the DHW sensor Package AD212 a Connect the domestic hot water looping pump to the MAUX outlet on the AD249 option z Low loss header e Boiler pump 4 4 5 Hot water storage tank con...

Page 19: ...tor in place delivered with the DHW sensor package AD212 Y Connect the DHW sensor Package AD212 U Connect the heating pump Circuit A I Solar sensor probe O Connect the solar station to the solar colle...

Page 20: ...g to the outside temperature The zone is reheated when the heating buffer temperature sensor E falls 6 C below the calculated set temperature Reheating in the heating zone stops when the heating buffe...

Page 21: ...the terminal block Z Reversal valve E Buffer tank load pump R Connect a domestic hot water tank if the storage tank O is only used for heating T Connect the DHW sensor Package AD212 Y Connect the DHW...

Page 22: ...W set point by the boiler The heating zone is maintained at the set temperature calculated according to the outside temperature The zone is reheated when the heating buffer temperature sensor falls 6...

Page 23: ...t in both cases Case 1 The control system regulates the primary circuit boiler exchanger and the secondary circuit exchanger pool 4 Connect the primary circuit pump boiler exchanger to the MB outlet o...

Page 24: ...AMB B 2 1 S AMB A 2 1 S SYST TA S ECS S EXT S DEP C 2 1 2 1 2 1 2 1 2 1 S DEP B 2 1 TS C AUX C SCU PCU On off OT BL RL PUMP 3 4 2 7 5 MODE r x 0 2 4 6 8 10 12 14 16 18 22 24 20 c MODE r x 0 2 4 6 8 1...

Page 25: ...ayed if INSTALLATION is set to EXTENDED 4 4 8 Connection in cascade n DHW tank after the mixing tank A Master boiler DIEMATIC iSystem Z Secondary boiler DIEMATIC iSystem or IniControl E Secondary boil...

Page 26: ...ORK 1 Installer level SYSTEM Menu ADD SLAVE 1 The parameter is only displayed if INSTALLATION is set to EXTENDED DIEMATIC iSystem Settings to be made for this type of installation Follower boilers Par...

Page 27: ...ller E Keys on which the function varies as and when selections are made F Rotary setting button 4 Turn the rotary button to scroll through the menus or modify a value 4 Press the rotary button to acc...

Page 28: ...Back to the previous level ESC Back to the previous level without saving the modifications made t Manual reset n Flame output level C002705 A The whole symbol flashes The burner starts up but the flam...

Page 29: ...Flashing symbol Temporary override 4 Steady symbol Permanent override m Reduced mode The symbol is displayed when a NIGHT override reduced is activated 4 Flashing symbol Temporary override 4 Steady sy...

Page 30: ...ar Permanent override n Other information r The symbol is displayed when domestic hot water production is running w Valve indicator The symbol is displayed when a 3 way valve is connected 4 x 3 way va...

Page 31: ...is also possible to access the installer level by pressing only the key for around 5 seconds bar 1 1 2 2 r c STD t v 0 2 4 6 8 10 12 14 16 18 22 24 20 pb AUTOxc r j M g m SUNDAY 11 45 C002219 D 04 ba...

Page 32: ...turn the rotary button 4 To modify the parameter press the rotary button To go back to the previous display press the key j bar 1 1 2 2 r c STD t v 0 2 4 6 8 10 12 14 16 18 22 24 20 pb AUTOxc r j M g...

Page 33: ...GE menu is displayed Select the desired language by turning the rotary button 5 To confirm press the rotary button bar 1 1 2 2 r c STD t v 0 2 4 6 8 10 12 14 16 18 22 24 20 pb AUTOxc r j L g m CURRENT...

Page 34: ...AL Displays the parameters of a conventional installation TRADITIONAL EXTENDED Displays all parameters Regardless of what is done to the keys the regulator switches back to TRADITIONAL mode after 30 m...

Page 35: ...pump ORDER BURNER The outlet MA is active when a burner demand is present FAILURE The outlet MA is active if an fault is detected DEF CASC Output MA is active if a default is present in one of the boi...

Page 36: ...AILURE REVISION The telephone outlet is closed in the event of revision display DEF REV The telephone outlet is closed in the event of failure or revision display CT TEL 1 CLOSE See table hereafter CL...

Page 37: ...ting CT TEL on the I TEL contact CT TEL I TEL C contact closed C contact open CLOSE ANTIFR The antifreeze mode is active on all boiler circuits The mode selected on the boiler is active 0 1 A The mode...

Page 38: ...The antifreeze mode is active on the circuits concerned The mode selected on the circuits is active 0 1 A B C The antifreeze mode is active on the circuits concerned The mode selected on the circuits...

Page 39: ...aracter or turn the rotary button to leave an empty space 6 Choose the other characters in the same way The input zone may contain up to 6 characters To move from one character to another turn the rot...

Page 40: ...dify the curve turn the rotary button 6 To confirm press the rotary button To cancel press key h 0 7 Heating curve set 1 1 2 2 r c STD t v 0 2 4 6 8 10 12 14 16 18 22 24 20 pb AUTOxc r j M g m SUNDAY...

Page 41: ...mperature for which the maximum water temperature in the circuit is reached T Value of the heating curve Select the parameter CIRC CURVE x Value set to the parameter HCZP D When you modify the heating...

Page 42: ...generator C T DHW BOTTOM 1 Water temperature in the bottom of the DHW tank C TEMP TANK AUX 1 Water temperature in the second DHW tank connected to the AUX circuit C DHW A TEMP 1 Water temperature in...

Page 43: ...C 1 5 to 30 C Desired room temperature in comfort periods on circuit C 20 C NIGHT TEMP C 1 5 to 30 C Desired room temperature in reduced periods on circuit C 16 C DHW TEMP 1 10 to 80 C Desired domesti...

Page 44: ...il the time indicated or all the time 7 7 Present time 1 hour HOLIDAYS 7 7 1 to 364 The antifreeze mode is active on all boiler circuits Number of days holiday xx 1 heating OFF xx xx 1 Restarting xx x...

Page 45: ...st and lighting on the display 1 To access user level Press the key 2 Select the menu SETTING 4 Turn the rotary button to scroll through the menus or modify a value 4 Press the rotary button to access...

Page 46: ...in March and back to winter time on the last Sunday in October AUTO MANU for countries where the time change is done on other dates or is not in use 1 According to the configuration 5 5 6 Selecting a...

Page 47: ...edule Description TIME PROG A PROG P2 A PROG P3 A PROG P4 A Timer programme for circuit A TIME PROG B PROG P2 B PROG P3 B PROG P4 B Timer programme for circuit B TIME PROG C PROG P2 C PROG P3 C PROG P...

Page 48: ...ode have been selected press the rotary button to confirm User level TIME PROGRAM Menu Day Comfort periods Filling enabled P1 _______________ P2 _______________ P3 _______________ P4 _______________ T...

Page 49: ...elect the menu ANNUAL PROG 4 Turn the rotary button to scroll through the menus or modify a value 4 Press the rotary button to access the selected menu or confirm a value modification For a detailed e...

Page 50: ...uit stopped OFF OFF A B A B C AC B C A B C SU A E B E A B W C E AC W B C W ALL BEG DATE N 01 Setting start date of the stop 01 1 31 BEG MONTH N 01 Setting start month of the stop 01 1 12 END DATE N 01...

Page 51: ...C A B C SU A E B E A B W C E AC W B C W ALL BEG DATE N 07 Setting start date of the stop 01 1 31 BEG MONTH N 07 Setting start month of the stop 01 1 12 END DATE N 07 Setting end date of the stop 01 1...

Page 52: ...in Spanish NEDERLANDS Display in Dutch POLSKY Display in Polish T RK Display in Turkish P CCK Display in Russian 5 6 2 Calibrating the sensors 1 To access user level Press the key 2 Select the menu S...

Page 53: ...rature has stabilised Room temperature of circuit B OFFSET ROOM B 3 4 1 5 0 to 5 0 C Room offset on circuit B Is used to set a room offset Make this setting 2 hours after switching on when the room te...

Page 54: ...yed if INSTALLATION parameter is set to EXTENDED 2 The parameter is only displayed if P DHW is set to PUMP Type of gas used Parameter Unit C 330 5 C 330 6 C 330 7 C 330 8 C 330 9 C 330 10 Gas H G20 MI...

Page 55: ...u 1 Parameter Adjustment range Description Factory setting Customer setting BURN MIN RUN 0 to 180 seconds Setting the burner minimum operation time In heating mode 30 seconds TIMER GENE P 1 1 to 30 mi...

Page 56: ...7 ANTICIP C 1 0 0 to 10 0 Activation and adjustment of the anticipation time ANTICIP A ANTICIP B ANTICIP C page 58 NO ROOM INFL C 1 0 to 10 Influence of room sensor C ROOM S INFL page 59 3 SCREED DRY...

Page 57: ...estic hot water pump The timing of the domestic hot water load pump shutdown prevents the boiler and the heating circuits overheating Only if a load pump is used 2 minutes ADAPT ON Automatic adaptatio...

Page 58: ...er pump starts ON DHW 5 OFF The function is deactivated OFF BOILER T In DHW mode the DHW load pump starts up only if the boiler temperature is higher than the DHW TEMP setpoint 5 C TEMP SYST In DHW mo...

Page 59: ...e at outside temperature 0 C starting from a residual room temperature corresponding to the reduced temperature setpoint Anticipation is optimized if a room sensor is connected The regulator will auto...

Page 60: ...e remote control fitted in a location with no influence 1 Slight influence 3 Average influence recommended 10 Room thermostat type operation n NIGHT This parameter is displayed if at least one circuit...

Page 61: ...mperature or sliding output If the input voltage is less than VMIN OFF 0 10V the boiler is off The boiler temperature setting corresponds strictly to the 0 10 V input The secondary boiler circuits con...

Page 62: ...NTER STAGE TIMER 2 1 to 30 min Time delay for starting up or shutting down generators 4 mn SLAVE NUMBER 5 2 to 10 Set the network address of the secondary generator 2 1 The menu is displayed only if t...

Page 63: ...to the previous list 7 Select NB NETWORK ELEMENTS This screen summarises the elements in the network recognized by the system Press j to go back to the previous list 1 1 2 2 r c STD t v 0 2 4 6 8 10...

Page 64: ...the generator sensors connected ROOM SENSOR Performs a RESET of the room sensors connected After reset TOTAL RESET and RESET EXCEPT PROG the control system goes back to the display of the language ch...

Page 65: ...Refer to the manual delivered with the boiler 3 To go back to the main display press key j2 times EMISSION MEASUREMENTS Menu Generator Function available Description Values displayed Generator name A...

Page 66: ...at maintenance is necessary on the date selected Set the date using the parameters below AUTO a Not applicable Do not select this setting REVISION HOUR 1 0 to 23 Time at which the REVISION display app...

Page 67: ...enu or confirm a value modification For a detailed explanation of menu browsing refer to the chapter Browsing in the menus page 31 3 Set the following parameters After Sales level SUPPORT Menu Paramet...

Page 68: ...le below Code Messages Description Checking solution B00 BL CRC PSU The PSU PCB is incorrectly configured Parameter error on the PSU PCB 4 Set the type of generator again in the menu CONFIGURATION Ref...

Page 69: ...rating correctly 4 Check whether the boiler sensor has been correctly fitted B07 BL DT OUTL RET Maximum difference between the flow and return temperature exceeded The water flow in the installation i...

Page 70: ...Check the supply pressure 4 Check the operation and setting of the gas valve unit 4 Check that the air inlet and flue gas discharge flues are not blocked 4 Check that there is no recirculation of flu...

Page 71: ...e a note of the code displayed The code is important for the correct and rapid diagnosis of the type of failure and for any technical assistance that may be needed 2 Press the t key If the code is dis...

Page 72: ...4 Check the wiring between the PCU PCB and the sensor 4 Check that the SU PCB is correctly in place 4 Check that the sensor has been correctly fitted Sensor fault 4 Check the Ohmic value of the sensor...

Page 73: ...Check the Ohmic value of the sensor 4 Replace the sensor if necessary No water circulation 4 Vent the air in the heating system 4 Check the circulation direction pump valves 4 Check the water pressur...

Page 74: ...n place 4 Check that the sensor has been correctly fitted Sensor fault 4 Check the Ohmic value of the sensor 4 Replace the sensor if necessary No water circulation 4 Vent the air in the heating system...

Page 75: ...nection 4 Check the wiring between the PCU PCB and the STB 4 Check that the SU PCB is correctly in place 4 Check the electrical continuity of the STB 4 Check whether the STB has been correctly fitted...

Page 76: ...king the gas supply pressure 4 Check the ionization ignition electrode 4 Check the earthing 4 Check the wiring on the ionization ignition electrode L15 CCE TST FAIL PCU The cyclical leak proofing kit...

Page 77: ...k for adequate draw on the chimney connection 4 Replace the fan if need be L35 BACK BOIL FAIL PCU Flow and return reversed Bad connection 4 Check that the sensor has been correctly fitted Sensor fault...

Page 78: ...rectly fitted Sensor fault 4 Check the Ohmic value of the sensor 4 Replace the sensor if necessary D05 OUTSI S FAIL SCU Outside temperature sensor fault Remarks The boiler operates on BOILER MAX tempe...

Page 79: ...alue of the sensor 4 Replace the sensor if necessary D14 MC COM FAIL SCU Communication failure between the SCU PCB and the boiler radio module Bad connection 4 Check the link and the connectors Boiler...

Page 80: ...k is no longer protected If a tank without Titan Active System is connected to the boiler check that the TAS simulation connector delivered with package AD212 is fitted to the sensor card D38 TA S DIS...

Page 81: ...key until PARAMETERS is displayed 2 Check the following parameters 4 Turn the rotary button to scroll through the menus or modify a value 4 Press the rotary button to access the selected menu or conf...

Page 82: ...P T C Temperature of the swimming pool water sensor on circuit C OUTSIDE TEMP 1 Outside temperature ROOMTEMP A 1 Room temperature of circuit A ROOMTEMP B 1 3 Room temperature of circuit B ROOMTEMP C...

Page 83: ...NCE Control system sequence See chapter Control system sequence page 83 HOT Index of the generator in the system TYPE Generator type R CTRL A 1 ON Presence of a remote control A OFF No remote control...

Page 84: ...FDU Generator type ENERGY METER OFF ON Activation of the Nominal Energy Estimate function MAX HEAT OUTP maximum permitted heating capacity MAX DHW OUTP maximum permitted domestic hot water flow MIN OU...

Page 85: ...mper 44 Stop fan 6 Switching off the boiler 60 Post operation time delay on the boiler pump 61 Stop boiler pump 62 Close isolating valve 63 Start anti short cycle 8 Stop 0 Awaiting burner start up 1 A...

Page 86: ......

Page 87: ......

Page 88: ...cza sp z o o PL www dedietrich cz www facebook com DeDietrichPL www dedietrich pl 420 271 001 627 dedietrich bdrthermea cz 48 71 71 27 400 biuro dedietrich pl MEIER TOBLER AG CH www meiertobler ch 41...

Reviews: