Pressure reducer
If the mains pressure exceeds 80% of the calibration of the valve or
safety unit (e.g. 5,5 bar (0,55 MPa) for a safety unit calibrated to 7 bar
(0,7 MPa)), a pressure reducer must be installed upstream of the
appliance. Install the pressure reducer downstream the water meter
in such a way as to ensure the same pressure in all of the installation
pipes.
n
Measures to take to prevent hot water flow return
Fit a one-way valve to the domestic cold water circuit.
5.9
Electrical connections
5.9.1.
Recommendations
WARNING
4
Only qualified professionals may carry out electrical
connections, always with the power off.
4
Earth the appliance before making any electrical
connections.
Make the electrical connections of the appliance according to:
4
The instructions of the prevailing standards,
4
The instructions on the circuit diagrams provided with the
appliance,
4
The manufacturer’s instructions.
Belgium
: The earthing must comply with the RGIE standard.
Germany
: The earth connection shall comply with standard
VDE 0100.
France
: The earth connection shall comply with standard
NFC 15-100.
Other countries
: The earthing shall comply with local standards.
CAUTION
4
Separate the sensor cables from the 230/400 V
circuit cables.
4
The installation must be fitted with a main switch.
5.9.2.
Connecting the domestic hot water sensor
Connect the DHW sensor to the corresponding terminal block on the
boiler (Terminal S.ECS).
¼
See chapter: "Terminal block", page 22.