Tab.10 Other data
Alezio G hybrid
24/28 MI
34/39 MI
Boiler weight (empty)
kg
26
28.5
at a distance of one metre
from the boiler
Central heating
operation
DHW operation
dB(A)
38
42
42
46
(1) Maximum
3.2.2
Heat pump
Maximum operating pressure: 0.3 MPa (3 bar)
Tab.11 Conditions of use
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Limit water operating
temperatures in heating
mode
+18 °C/+55 °C
+18 °C/+60 °C
+18 °C/+60 °C
Outdoor air operating
temperature limits in
heating mode
-15° C/+35 °C
-15° C/+35 °C
-20° C/+35 °C
Water operating temper
ature limits in cooling
mode
+7°C / +25°C
+7°C / +25°C
+7°C / +25°C
Outdoor air operating
temperature limits in
cooling mode
+7 °C/ +46 °C
+7 °C/ +46 °C
+7 °C/ +46 °C
Tab.12 Heating mode: outside air tempe7°C, water temperature at the 35°C. Performances in accordance with
EN 14511-2.
Measurement type
Unit
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Heat output
kW
4.6
5.82
7.90
Coefficient of perform
ance (COP)
5.11
4.22
4.34
Absorbed electrical
power
kWe
0.90
1.38
1.82
Nominal water flow rate
(ΔT = 5 K)
m
3
/hour
0.80
1.00
1.36
Tab.13 Heating mode: outside air tempe2 °C, water temperature at the 35 °C. Performances in accordance
with EN 14511-2.
Measurement type
Unit
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
Heat output
kW
3.47
3.74
6.80
Coefficient of perform
ance (COP)
3.94
3.37
3.30
Absorbed electrical
power
kWe
0.88
1.11
2.06
3 Technical specifications
18
7611444 - v06 - 04032019