6 Technical specifications
6.1
Technical specifications
6.1.1.
Electricity supply
230 V AC (+/- 10%) - 50 Hz
6.1.2.
Heat pump
Conditions of use:
4
Limit operating temperatures in Hot mode:
-
Water: +18 °C / +55 °C
-
Outside air:
-15 °C / +35 °C (AWHP 6 MR, 8 MR)
-20 °C / +35 °C (AWHP 11-27)
4
Limit operating temperatures in Cooling mode:
-
Water: +7 °C / +25 °C
-
Outside air: +15 °C / +40 °C (At less than 18°C, it is necessary
to use the HK24 insulation kit option)
4
Maximum operating pressure: 3 bar
AWHP
6 MR
8 MR
11 MR 11 TR
14 MR 14 TR
16 MR 16 TR
22 TR
27 TR
Calorific output -
A7/W35
(1)
kW
6.0
8.5
10.9
10.9
13.7
13.7
15.7
15.7
19.4
24.4
COP hot - A7/
W35
(1)
4.00
4.10
4.23
4.23
4.03
4.03
3.90
3.90
3.94
3.90
Absorbed
electrical power -
A7/W35
(1)
kWe 1.5
2.1
2.6
2.6
3.4
3.4
4.03
4.03
4.9
6.3
Nominal
amperage - A7/
W35
(1)
A
6.8
9.2
11.2
6.7
14.8
8.8
17.6
10.1
12.3
15.6
Calorific output -
A2/W35
(2)
kW
4.4
5.9
7.6
7.6
10.3
10.3
10.4
10.4
11.6
14.7
COP hot - A2/
W35
(2)
3.12
3.12
3.10
3.10
3.10
3.10
3.10
3.10
3.11
3.10
Absorbed
electrical power -
A2/W35
(2)
kWe 1.4
1.9
2.5
2.5
3.3
3.3
3.4
3.4
3.9
4.7
(1) Hot mode: Outside air tempe7 °C, Water temperature at the 35 °C. Performances in line with EN 14511-2.
(2) Hot mode: Outside air tempe2 °C, Water temperature at the 35 °C. Performances in line with EN 14511-2.
(3) Cooling mode: Outside air tempe35 °C, Water temperature at the 18 °C. Performances in line with EN 14511-2
(4) 5 m from the appliance, free field.
(5) Test conducted in accordance with the standard NF EN 12102