53
De Dietrich Gas 310/610 ECO
13.1.2 Pump run on time (
)
Pump run on time can be adjusted (Please refer to
installation contractor)
-Press the
-key until the digit
(with dot) appears in the
code
-display.
-Press the
-key until the digit
(with dot) appears in
the
code
-display.
-Set the required value, using the [+] and [-]-keys.
▪
Press the
-key to stare the new value (value will flash twice).
▪
Press the
reset
-key to return to operating mode.
Table 18 Adjustments pump run on time
13.1.3 Boiler control (
)
Setting mode, parameter
, can be set to different values
(see table 19).
Proceed as follows to change the boiler control:
▪
Press the
key until the number
(with dot)
appears in the
code
window.
▪
Press the
key until the letter
(with dot)
appears in the
code
window.
▪
Use the [+] and/or [-] keys to specify the required
setting.
▪
Press the
key to stare the new setting (flashes twice to confirm).
▪
Press the
reset
key once to return to operating mode.
Table 19 Boiler control settings.
Example:
boiler control
indicates that the boiler is controlled by means of a 0-10 volt signal modulated on the
basis of flow temperature (
= 4). Heat demand is on (
= 1).
13.2 Setting mode service level (only for the qualified service engineer) (
)
To prevent accidental, unauthorized access by non-qualified persons the control system requires an input code to
gain access to the second level of boiler control.
-Press the
and
keys simultaneously and hold. The
code
-display now shows a letter
with a random
number in the
-display.
-While holding both keys pressed, set the
-display to
, using the [+] or [-] keys and press the
key.
-The display will flash twice, confirming acceptance of the access code.
-Release the keys and
will disappear from the display.
Important!!
Changing the pre-set values without reference to the tables contained in this manual may result
in incorrect boiler operation.
•
The service settings can now be reached by pressing the
-key until the digit
(with dot) appears in the
code
-display. Set the required value, using the
key.
•
To deletes the service code, press the
reset
-key once.
•
If no keys are pressed over a 15 minute period, the service code will delete automatically.
Code
Description
Pump post purge = 10 seconds
Pump purge time for 1 to 15 minutes
(
=
to
)
Continuous pump operation
Code
Description
heat demand off
Heat demand on
on/off and High/Low
on/off and modulated on flow temperature
External 0-10v analog signal on temperature
External 0-10v analog signal on output %
Summary of Contents for 310 ECO Series
Page 32: ...31 De Dietrich Gas 310 610 ECO 8 4 Wiring Diagram fig 18 wiring diagram Fb 12AT ...
Page 33: ...32 De Dietrich Gas 310 610 ECO 8 4 Wiring Diagram Continued ...
Page 70: ...69 De Dietrich Gas 310 610 ECO 16 ADDENDICES ...
Page 71: ...70 De Dietrich Gas 310 610 ECO 16 1 Control menu Fig 40 Control menu flow chart ...
Page 72: ...71 De Dietrich Gas 310 610 ECO 16 2 Shut off codes ...
Page 73: ...72 De Dietrich Gas 310 610 ECO 16 2 Shut off codes Continued Table 25 Shut off codes ...