De Dietrich Gas 310/610 ECO
13.0 SETTING MODE
13.1 User level setting mode (
)
Setting mode is used to change various settings to suit individual requirements. The required code is selected by
pressing the
key until
appears in the
code
window. Select the required code with the
key. Now press
the [+] key to increase a setting or the [-] key to decrease a setting.
Press the
key to stare the new setting. The new value will flash twice in the
window to confirm the setting.
Cede Description
Setting range and explanation if
necessary
Factory setting
Flow temperature set point (see
section 13.1.1)
-
= 68 – 194°F or
-
[20-90°C]
Boiler operating limit set point, also maximum
setting if external control is used.
= 176°F
= 80°C
Pump post purge setting
(see section 13.1.2)
= Pump post purge = 10 seconds
-
= pump run on in minutes
= Pump operates continuously
Boiler control setting
(see section 13.1.3)
Control mode (modulating, on/off, etc.)
Important!!
Changing
and
should only be 0n design engineer’s advice.
13.1.1 Flow temperature (
)
The required flow temperature is adjustable from 68-194°F [20-90°C].
The following diagram shows a typical example of this procedure:
Table 17 Settings mode user level
Fig. 26 Setting flow temperature
Summary of Contents for 310 ECO Series
Page 32: ...31 De Dietrich Gas 310 610 ECO 8 4 Wiring Diagram fig 18 wiring diagram Fb 12AT ...
Page 33: ...32 De Dietrich Gas 310 610 ECO 8 4 Wiring Diagram Continued ...
Page 70: ...69 De Dietrich Gas 310 610 ECO 16 ADDENDICES ...
Page 71: ...70 De Dietrich Gas 310 610 ECO 16 1 Control menu Fig 40 Control menu flow chart ...
Page 72: ...71 De Dietrich Gas 310 610 ECO 16 2 Shut off codes ...
Page 73: ...72 De Dietrich Gas 310 610 ECO 16 2 Shut off codes Continued Table 25 Shut off codes ...