DeDietrich 200 ESL HYBRID 4-8 User Manual Download Page 16

3  Technical specifications

3.1 

Homologations

3.1.1 

Directives

This product complies with the requirements of the following European 

Directives and Standards:

Pressure Equipment Directive 2014/68/EU
Low Voltage Directive 2014/35/EU

Generic standard: EN 60335-1

Relevant standard: EN 60335-2-40
Electromagnetic Compatibility Directive 2014/30/EU

Generic standards: EN 61000-6-3, EN 61000-6-1

Relevant Standard: EN 55014
Standard DIN 1988 (TWRWI): technical regulations for drinking water 

installations

This product conforms to the requirements of European Directive 

2009/125/EC on the ecodesign of energy-related products.
In addition to the legal requirements and guidelines, the supplementary 

guidelines in this manual must also be followed.
Supplements or subsequent regulations and guidelines that are valid at 

the time of installation shall apply to all regulations and guidelines 

specified in this manual.

3.2 

Technical data

3.2.1 

Heat pump

Maximum operating pressure: 0.3 MPa (3 bar)

Tab.3

Conditions of use

 

AWHP 4.5 MR

AWHP 6 MR-3

AWHP 8 MR-2

AWHP 11 MR-2 

AWHP 11 TR-2

AWHP 16 MR-2 

AWHP 16 TR-2

Limit water op­

erating temper­

atures in heat­

ing mode

+18 °C/+55 °C

+18 °C/+60 °C

+18 °C/+60 °C

+18 °C/+60 °C

+18 °C/+60 °C

Outdoor air op­

erating temper­

ature limits in 

heating mode

-15° C/+35 °C

-15° C/+35 °C

-20° C/+35 °C

-20° C/+35 °C

-20° C/+35 °C

Water operat­

ing temperature 

limits in cooling 

mode

+7°C / +25°C

+7°C / +25°C

+7°C / +25°C

+7°C / +25°C

+7°C / +25°C

Outdoor air op­

erating temper­

ature limits in 

cooling mode

+7 °C/ +46 °C

+7 °C/ +46 °C

+7 °C/ +46 °C

+7 °C/ +46 °C

+7 °C/ +46 °C

3  Technical specifications

16

200 ESL HYBRID

7613346 - v06 - 02072019

Summary of Contents for 200 ESL HYBRID 4-8

Page 1: ...EASYLIFE SUSTAINABLE COMFORT MW 8200024 1 ALEZIO O HYBRID en User Guide Hybrid air water heat pump ALEZIO O HYBRID 200 ESL HYBRID 4 8 200 ESL HYBRID 11 16...

Page 2: ...sing the product and keep it in a safe place for later reference In order to ensure continued safe and efficient operation we recommend that the product is serviced regularly Our service and customer...

Page 3: ...anel description 26 4 4 1 Description of the keys 26 4 4 2 Description of the display 26 5 Operation 29 5 1 Use of the control panel 29 5 1 1 Browsing in the menus 29 5 2 Start up 29 5 3 Shutdown 30 5...

Page 4: ...odes 52 8 1 2 Fault codes 53 8 1 3 Alarm codes 54 8 2 Accessing the error memory 54 8 3 Troubleshooting 55 9 Decommissioning and disposal 57 9 1 Decommissioning procedure 57 9 2 Disposal and recycling...

Page 5: ...n accordance with prevailing local and national regulations Warning Do not touch the refrigeration connection pipes with your bare hands while the heat pump is running Danger of burn or frost injury W...

Page 6: ...ion Pursuant to Article L 113 3 of the French Consumer Code the installation of equipment must be done by a certified operator whenever the refrigerant load is in excess of two kilograms or when a ref...

Page 7: ...t refer to the chapter Setting the domestic hot water temperature set point Caution Pressure limiter device refer to the chapter Special precautions to be taken when connecting the domestic hot water...

Page 8: ...he wiring according to the wiring schematics described in the chapter Electrical Connections Installation and Service Manual Caution This appliance must be connected to the protective earth Earthing m...

Page 9: ...carry out electrical connections always with the power off Caution Separate the very low voltage cables from the 230 400 V circuit cables Important The frost protection function does not work if the...

Page 10: ...ithout the written consent of the manufacturer Caution To benefit from extended warranty cover no modifications must be made to the appliance Caution Do not neglect to service the heat pump Contact a...

Page 11: ...e skin Treat frost injuries like burns Rinse with copious amounts of tepid water do not remove clothing risk of adhesion to the skin If skin burns appear call a doctor immediately In the event of cont...

Page 12: ...glasses with side protection Skin protection clothing made principally of cotton Industrial hygiene do not drink eat or smoke at the place of work Considerations on dis posal Important Disposal must...

Page 13: ...rds Carry out initial commissioning and any checks necessary Explain the installation to the user If maintenance is necessary warn the user of the obligation to check the appliance and keep it in good...

Page 14: ...ecial instructions We do this to improve user safety to prevent problems and to guarantee correct operation of the appliance Danger Risk of dangerous situations that may result in serious personal inj...

Page 15: ...rd 230 V 3 Heating circuit flow 4 Circuit B flow 5 Heating circuit return 6 Circuit B return optional 7 Connection for recirculation 8 Domestic hot water outlet 9 Return from the indoor module to the...

Page 16: ...guidelines in this manual must also be followed Supplements or subsequent regulations and guidelines that are valid at the time of installation shall apply to all regulations and guidelines specified...

Page 17: ...rm ance COP 3 97 3 37 3 30 3 19 3 19 3 27 3 27 Absorbed electrical power kWe 0 88 1 11 2 06 3 19 3 19 3 94 3 94 Tab 6 Cooling mode outside air temperature 35 C water temperature at the outlet 18 C Per...

Page 18: ...water 45 C for AWHP 4 5 MR only inner and outer sides 3 Quantity of refrigerant calculated in tonnes of CO2 equivalent Important The values in tonnes of CO2 equivalent are calculated using the follow...

Page 19: ...0 3 2 4 Combination heaters with medium temperature heat pump Tab 13 Technical parameters for heat pump combination heaters parameters declared for medium temperature application Product name 200 ESL...

Page 20: ...emperature WTOL C 80 80 Electrical power consumption Off mode POFF kW 0 009 0 009 Thermostat off mode PTO kW 0 049 0 049 Stand by PSB kW 0 013 0 019 Crankcase heater mode PCK kW 0 055 0 055 Supplement...

Page 21: ...Prated kW 11 15 22 Rated heat output under colder conditions 1 1 Prated kW 9 11 15 Rated heat output under warmer conditions 1 1 Prated kW 6 8 13 Declared capacity for heating for part load at an indo...

Page 22: ...8 10810 10 Annual energy consumption under warmer conditions QHE kWh GJ 1904 0 2580 0 4120 0 Rated air flow rate outdoors for air to water heat pumps m3 h 3300 6000 6000 Declared load profile L L L Da...

Page 23: ...c metres per hour m3 h 3 Available pressure for 4 to 8 kW outdoor units 4 Available pressure for the 11 and 16 kW outdoor units Fig 4 Pressure available MW 2000147 2 0 1 3 4 2 0 5 1 0 1 5 2 0 2 5 1 2...

Page 24: ...rface which comes into contact with drinking water is enamelled The indoor module is insulated by chlorofluorocarbon free polyurethane foam which helps to keep heat losses to a minimum 4 2 Operating p...

Page 25: ...ol system PCB 2 Immersion sleeve for the top domestic hot water sensor 3 Flow meter 4 Plate exchanger condenser part of the heat pump 5 Immersion sleeve for the bottom domestic hot water sensor 6 3 wa...

Page 26: ...nabled Flashing symbol heating production running Steady symbol domestic hot water function enabled Flashing symbol domestic hot water production running Heating or cooling function disabled Domestic...

Page 27: ...t water production Sub Menu CLOCK PCB selection menu access to information on the additional PCBs connected Display of PCB names The name of the PCB for which the parameters are displayed is scrolling...

Page 28: ...utside temperature sensor connected fixed symbol for WINTER mode flashing symbol for SUMMER mode Other Information Test Menu forced operation in heating and cooling mode Three way valve connected Thre...

Page 29: ...e when the icons flash Press the key to access the next menu access the next sub menu access the next parameter increase the value Press the key to access the previous menu access the previous sub men...

Page 30: ...3 Confirm by pressing the key 4 Select the heating shut down pressing the key The screen displays The frost protection function continues to run The heating has been shut down Important Press the key...

Page 31: ...the main display by pressing the h key Important The display disappears after a few seconds of inactivity 5 3 3 Shutting down the cooling function Important If the heating function is shut off then th...

Page 32: ...is lower than 3 C the back up starts up If the water temperature is higher than 10 C the back up shuts down and the circulating pump continues to run for a short time The radiator valves in rooms whe...

Page 33: ...of the PCB or circuit 3 Setting parameters Tab 16 List of User sub menus Sub menu Description Name of the PCB or circuit CIRCA Main heating circuit EHC 04 CIRCB Additional heating circuit B SCB 04 DH...

Page 34: ...e cooling activity zone 3 Can be set from 20 C to 30 C 25 25 CP143 Setpoint of the room cooling temperature of the zone cooling activity zone 4 Can be set from 20 C to 30 C 25 25 CP144 Setpoint of the...

Page 35: ...int from the Domestic Hot Water tank Can be set from 40 C to 65 C 54 DP080 Reduced temperature setpoint from the Domestic Hot Water tank Can be set from 10 C to 60 C 10 DP200 DHW primary mode current...

Page 36: ...09 kWh HP064 Cost of fossil energy oil or gas price per litre or per m3 Cost of fossil energy oil or gas price per litre or per m3 Can be set from 0 01 to 2 50 kWh 0 90 kWh 6 2 4 User menu CU OH 04 AP...

Page 37: ...or the main heating circuit CIRCB Timer programming for the additional heating circuit B DHW Timer programming for the domestic hot water circuit CLK Setting the clock and the date COUNTERS TIME PROG...

Page 38: ...tage of backup hours X AC030 Total startings of the first stage of backup X AC031 Total startings of the second stage of backup X DC002 Numbers of Domestic Hot Water diverting valve cycles X X DC003 N...

Page 39: ...to 31 available MONTH Can be set from 1 to 12 available YEAR Can be set from 2000 to 2100 available 6 3 Setting the parameters 6 3 1 Setting the room temperature set point in comfort mode Important Th...

Page 40: ...et point by pressing the key Go back to the main display by pressing the h key 6 3 3 Activating Forcing of the cooling function The cooling function can be managed via the PROG COOL sub menu dedicated...

Page 41: ...mperature set point by pressing the or key 3 Confirm the new value of the heating water temperature set point by pressing the key 4 Go back to the main display by pressing the h key Important To force...

Page 42: ...es Day selected Description every day of the week Monday Tuesday Wednesday Thursday Friday Saturday Sunday Important The key is used to move to the right The key is used to move to the left 6 Confirm...

Page 43: ...on circuit A Choose the EHC 04 menu Measured values on circuit B Choose the SCB 04 menu Measured values connected to the operation of the heat pump Choose the EHC 04 menu Values measured connected to...

Page 44: ...M001 Domestic Hot Water tank temperature bottom sensor C X X DM006 Domestic Hot Water tank temperature top sensor X DM009 Automatic derogation status of Domestic Hot Water mode 0 Scheduling 1 Manual 2...

Page 45: ...down system pump operation 65 compressor bypass The back ups are operating 66 the temperature exceeds the compressor s maximum operating tempera ture The compressor has stopped The back ups are operat...

Page 46: ...g running The compressor is running 70 defrosting conditions not met The compressor has stopped The back ups are operating 71 defrosting running The compressor and the back ups are running 88 BL Back...

Page 47: ...ited If the heating set point on the heat pump differs from the system set point 60 pump post operation Heat pump and back up shut down system pump running 65 compressor bypass The back ups are operat...

Page 48: ...the compressor s maximum operating tempera ture The compressor has stopped The back ups are operating 67 the outside temperature is lower than the compressor s maximum operat ing temperature The comp...

Page 49: ...ot met The compressor has stopped The back ups are operating 71 defrosting running The compressor and the back ups are running 17 DeAiration 30 normal operation The compressor or the back ups are runn...

Page 50: ...7 1 1 Troubleshooting Caution All work on the refrigeration circuit must be done by a qualified professional according to prevailing codes of practice and safety in the profession recovery of the refr...

Page 51: ...7 2 1 Cleaning the casing 1 Clean the outside of the appliance using a damp cloth and a mild detergent 7 Maintenance 7613346 v06 02072019 200 ESL HYBRID 51...

Page 52: ...contact a maintenance technician Tab 32 List of temporary error codes Error code Message Description H00 00 SENS T FLOW OPEN Boiler flow sensor in open circuit Heat pump flow sensor defective H00 01...

Page 53: ...e code E30 H02 27 FLUE GAS TEMPERATURE SWITCH BLOCKING Maximum flue gas temperature exceeded If this message is generated 5 times in less than 24 hours the appliance locks down and displays the code E...

Page 54: ...times in 24 hours E02 29 FLUE GAS TEMPERATURE SWITCH ERROR Maximum flue gas temperature exceeded 5 times in 24 hours E02 41 FLUE TEMPERATURE PRESSURE SWITCH PRESENT Presence of a flue gas pressure sw...

Page 55: ...old The heating set point tem perature is too low Increase the value of parameter or if a room thermostat is connec ted increase the temperature on it The heating mode is deac tivated Activate the hea...

Page 56: ...rrect the error if possible The water pressure is too low 1 bar Not enough water in the installation Top up the system with water Water leak Contact the installer Clicking in the central heating pipes...

Page 57: ...manently 1 Contact the installer 9 2 Disposal and recycling Warning Removal and disposal of the heat pump must be carried out by a qualified professional in accordance with prevailing local and nation...

Page 58: ...ehind the radiators to prevent heat losses Insulate the pipes in rooms that are not heated cellars and lofts Close the radiators in rooms not in use Do not run hot or cold water pointlessly Install an...

Page 59: ...r climate conditions kW 4 3 6 4 6 5 Space heating Annual energy consumption under colder warmer climate conditions kWh GJ 3008 970 3 0 4564 1299 4 0 4236 1544 3 0 Water heating Annual energy consumpti...

Page 60: ...colder warmer climate conditions kWh 2 GJ 3 1432 664 0 0 1432 664 0 0 1432 664 0 0 Seasonal space heating energy efficiency under colder warmer climate conditions 124 169 122 167 119 161 Water heatin...

Page 61: ...lass III 1 5 Class IV 2 Class V 3 Class VI 4 Class VII 3 5 Class VIII 5 Temperature control Seasonal space heating energy efficiency of heat pump 1 If tank rating is above A use 0 95 from fiche of boi...

Page 62: ...tween the two adjacent values 2 Prated is related to the preferential space heater or combination heater Tab 39 Package efficiency temperature regulator heat pump 200 ESL Hybrid 4MR EFU C 19 200 ESL H...

Page 63: ...hnological information contained in these technical instructions as well as any drawings and technical descriptions supplied remain our property and shall not be multiplied without our prior consent i...

Page 64: ...s C Salvador Espriu 11 08908 L HOSPITALET de LLOBREGAT BDR THERMEA Czech Republic s r o CZ DE DIETRICH Technika Grzewcza sp z o o PL www dedietrich cz www facebook com DeDietrichPL www dedietrich pl 4...

Reviews: