User Guide

Hybrid heat pump

HPI G HYBRID

200 ASL HYBRID 4–8

200 ASL HYBRID 11–16

Summary of Contents for 200 ASL HYBRID 11-16

Page 1: ...ADVANCE SUSTAINABLE COMFORT MW 8200025 3 HPI G HYBRID MW 8200025 3 en User Guide Hybrid heat pump HPI G HYBRID 200 ASL HYBRID 4 8 200 ASL HYBRID 11 16...

Page 2: ...sing the product and keep it in a safe place for later reference In order to ensure continued safe and efficient operation we recommend that the product is serviced regularly Our service and customer...

Page 3: ...in components 26 4 4 Description of the control panel 27 4 4 1 Description of the keys 27 4 4 2 Description of the display 27 5 Operation 30 5 1 General 30 5 2 Use of the control panel 30 5 2 1 Browsi...

Page 4: ...8 3 1 Lxx type errors 51 8 4 Troubleshooting 51 9 Decommissioning and disposal 53 9 1 Decommissioning procedure 53 9 2 Disposal and recycling 53 10 Environmental 54 10 1 Energy savings 54 11 Warranty...

Page 5: ...local and national regulations Warning Do not touch the refrigeration connection pipes with your bare hands while the heat pump is running Danger of burn or frost injury Warning Do not touch the radi...

Page 6: ...rtant Allow the space required to install the appliance correctly refer to the chapter Dimensions of the Appliance Installation and Service Manual Caution Refrigerant safety Danger In the event of a r...

Page 7: ...t refer to the chapter Setting the domestic hot water temperature set point Caution Pressure limiter device refer to the chapter Special precautions to be taken when connecting the domestic hot water...

Page 8: ...he wiring according to the wiring schematics described in the chapter Electrical Connections Installation and Service Manual Caution This appliance must be connected to the protective earth Earthing m...

Page 9: ...carry out electrical connections always with the power off Caution Separate the very low voltage cables from the 230 400 V circuit cables Important The frost protection function does not work if the...

Page 10: ...ater and pressure in the heating installation Important Keep this document close to the place where the appliance is installed Caution Do not make any modifications to the heat pump without the writte...

Page 11: ...R410A Hazard identification Effects harmful to health The vapours are heavier than air and may lead to asphyxia owing to reduced oxygen levels Liquefied gas contact with the liquid may cause serious f...

Page 12: ...e may form under certain temperature and pressure conditions Toxic and corrosive vapours may be released by the effect of the heat Special intervention methods cool the volumes exposed to heat with wa...

Page 13: ...C No 842 2006 1 4 Liabilities 1 4 1 Manufacturer s liability Our products are manufactured in compliance with the requirements of the various Directives applicable They are therefore delivered with th...

Page 14: ...mum operation of the system you must abide by the following instructions Read and follow the instructions given in the manuals provided with the appliance Call on a qualified professional to carry out...

Page 15: ...ecial instructions We do this to improve user safety to prevent problems and to guarantee correct operation of the appliance Danger Risk of dangerous situations that may result in serious personal inj...

Page 16: ...rd 230 V 3 Heating circuit flow 4 Circuit B flow 5 Heating circuit return 6 Circuit B return optional 7 Connection for recirculation 8 Domestic hot water outlet 9 Return from the indoor module to the...

Page 17: ...Technical data 3 2 1 Heat pump Maximum operating pressure 0 3 MPa 3 bar Tab 3 Conditions of use AWHP 4 5 MR AWHP 6 MR 3 AWHP 8 MR 2 AWHP 11 MR 2 AWHP 11 TR 2 AWHP 16 MR 2 AWHP 16 TR 2 Limit water op...

Page 18: ...ormances in accordance with EN 14511 2 Measure ment type Unit AWHP 4 5 MR AWHP 6 MR 3 AWHP 8 MR 2 AWHP 11 MR 2 AWHP 11 TR 2 AWHP 16 MR 2 AWHP 16 TR 2 Cooling out put kW 3 80 4 69 7 90 11 16 11 16 14 4...

Page 19: ...R410A gas is 2088 3 2 2 Domestic hot water tank Tab 8 Technical specifications primary circuit heating water Specification Unit Value Maximum operating temperature Version with hydraulic back up C 90...

Page 20: ...lementary heater Yes Yes Heat pump combination heater Yes Yes Rated heat output under average conditions 1 Prated kW 8 8 Rated heat output under colder conditions 1 Prated kW 6 6 Rated heat output und...

Page 21: ...LWA dB 49 61 48 64 Annual energy consumption under average conditions QHE kWh GJ 4045 6 4312 7 Annual energy consumption under colder conditions QHE kWh GJ 4564 3 4236 3 Annual energy consumption und...

Page 22: ...W 6 1 8 2 11 8 Tj 7 C Pdh kW 6 4 9 0 12 9 Tj 12 C Pdh kW 6 5 10 1 15 4 Tj bivalent temperature Pdh kW 6 1 8 2 11 8 Tj operation limit temperature Pdh kW 5 6 6 2 8 3 Bivalent temperature Tbiv C 2 2 2 D...

Page 23: ...Wh GJ 1904 0 2580 0 4120 0 Rated air flow rate outdoors for air to water heat pumps m3 h 3300 6000 6000 Declared load profile L L L Daily electricity consumption Qelec kWh 4 816 4 816 4 816 Annual ele...

Page 24: ...c metres per hour m3 h 3 Available pressure for 4 to 8 kW outdoor units 4 Available pressure for the 11 and 16 kW outdoor units Fig 4 Pressure available MW 2000147 2 0 1 3 4 2 0 5 1 0 1 5 2 0 2 5 1 2...

Page 25: ...which comes into contact with drinking water is enamelled The indoor module is insulated by chlorofluorocarbon free polyurethane foam which helps to keep heat losses to a minimum 4 2 Operating princi...

Page 26: ...CB EHC 02 2 Immersion sleeve for the top domestic hot water sensor 3 Flow meter 4 Plate exchanger condenser part of the heat pump 5 Immersion sleeve for the bottom domestic hot water sensor 6 3 way va...

Page 27: ...rameter scrolling Help available Display the curve of the selected parameter Resetting the timer programs to zero Selection of the time range in comfort mode Selection of the time range in reduced mod...

Page 28: ...ammed MANUEL mode activated Domestic hot water override A vertical bar is displayed at bottom left when a domestic hot water override is activated Fig 11 Indicator MW 3000171 2 bar r 1 2 c 1 2 v 16 18...

Page 29: ...ar 1 1 2 2 r c STD t v pb w r r j M AUTOxc g m bar 1 1 2 2 r r c STD STD STD STD STD STD STD STD v p p p p p pb b b b b b b w w r r r r r r r r r AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUTO AUT AUT x xc g...

Page 30: ...go back to the previous display press the key It is possible to use the and keys instead of the settings button Press the settings button to confirm a menu a parameter a value Important To cancel an i...

Page 31: ...ctricity to the hybrid system 3 Shut off the gas supply 4 Keep the area frost free Warning In very low temperatures the installation may freeze if shut down It is preferable to keep the installation r...

Page 32: ...5 to 30 C 16 C DAY TEMP C Desired room temperature in DAY mode on circuit C Can be set from 5 to 30 C 20 C NIGHT TEMP C Desired room temperature in NIGHT mode on circuit C Can be set from 5 to 30 C 16...

Page 33: ...s actually connected Tab 16 Menu MODE Parameters Description Factory setting Customer setting FORCE AUTO An operating mode override is activated on the remote con trol optional To force every circuit...

Page 34: ...in the bottom of the second domestic hot water tank connec ted to the Auxiliary circuit C TEMPERATURE DCW Domestic cold water temperature C SWIMMING P T B Water temperature of the swimming pool on cir...

Page 35: ...ogram applied to circuit C P1 P2 P3 P4 TIME PROGRAM menu User Level Tab 20 Menu TIME PROGRAM Parameters Comfort period Loading enabled TIME PROG A PROG P2 A PROG P3 A PROG P4 A TIME PROG B PROG P2 B P...

Page 36: ...tions circuits or sensors actually connected Tab 22 Menu SETTING Parameters Description Factory setting Customer setting CONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT the screen is i...

Page 37: ...ure on circuit B OFFSET ROOM C Room temperature offset on circuit C Is used to set a room temperature offset Make this setting 2 hours after switching on when the room temperature has stabilised Can b...

Page 38: ...selected ALL all circuits are selected Tab 24 STOP N 1 Parameters Description Factory setting Customer setting BEG DATE N 01 BEG MONTH N 01 END DATE N 01 END DATE N 01 Shut down start date can be set...

Page 39: ...BEG MONTH N 07 END DATE N 07 END MONTH N 07 Shut down start date can be set from 1 to 31 Shut down start month can be set from 1 to 12 Shut down end date can be set from 1 to 31 Shut down end month c...

Page 40: ...y consump tion CO2 The hybrid control system optimises run ning according to the quantity of CO2 emitted NO COST HIGH TARIFF 1 Cost of peak time electricity 0 13 COST LOW TARIFF 1 Cost of off peak ele...

Page 41: ...rm the selection by pressing the settings button Important Go back to the previous display by pressing the key 4 Modify the value of the parameter by turning the settings button 5 Confirm the modifica...

Page 42: ...u is used to customise a timer program and to choose new time ranges 1 Go to the User level by pressing the key 2 Select the TIME PROGRAM menu by turning the settings button 3 Confirm the selection by...

Page 43: ...main display by pressing the key twice The new time range is highlighted at the top of the display 6 2 6 Calibrating the sensors 1 Go to the User level by pressing the key 2 Select the SETTING menu b...

Page 44: ...gs button Important Cancel the input by pressing the key 8 Go back to the main display by pressing the key 6 2 8 Setting the time and date 1 Go to the User level by pressing the key 2 Select the TIME...

Page 45: ...rk on the refrigeration circuit must be done by a qualified professional according to prevailing codes of practice and safety in the profession recovery of the refrigerant brazing under nitrogen All b...

Page 46: ...7 3 Cleaning the casing 1 Clean the outside of the appliance using a damp cloth and a mild detergent 7 Maintenance 46 200 ASL HYBRID 7613348 v06 10122018...

Page 47: ...note of the code displayed The code is important for the correct and rapid diagnosis of the type of error and for any technical assistance that may be needed 2 Press the key to clear the fault 3 If t...

Page 48: ...ture on the circuit down stream of the valve is still maintained the valves can be adjusted manually and do mestic hot water heating is still maintained Contact the professional responsible for mainte...

Page 49: ...ter tank without the Titan Active System is connected Contact the professional responsible for maintenance of the heat pump TA S DISCONNEC D38 The Titan Active System is in open circuit Production of...

Page 50: ...on the hybrid heat pump s flow sensor or sensor missing Contact the professional responsible for maintenance of the heat pump BL FLOW SENS MISS B28 Error on the hybrid heat pump s flow sensor or senso...

Page 51: ...nal responsible for maintenance of the heat pump 8 4 Troubleshooting Problems Probable causes Corrections The radiators are cold The heating set point tem perature is too low Increase the value of par...

Page 52: ...temperature on it The heat pump is not op erating Check that the heat pump is switched on Check the fuses and switches on the electrical installation The water pressure is too low 1 bar Top up the sy...

Page 53: ...ermanently 1 Contact the installer 9 2 Disposal and recycling Warning Removal and disposal of the heat pump must be carried out by a qualified professional in accordance with prevailing local and nati...

Page 54: ...ehind the radiators to prevent heat losses Insulate the pipes in rooms that are not heated cellars and lofts Close the radiators in rooms not in use Do not run hot or cold water pointlessly Install an...

Page 55: ...ble for material damage intangible losses or physical injury resulting from an installation that does not comply with Legal or regulatory requirements or provisions laid down by the local authorities...

Page 56: ...gy consumption under colder warmer cli mate conditions kWh GJ 4564 1299 3 0 4236 1544 3 0 Water heating Annual energy consumption under colder warmer cli mate conditions kWh 2 GJ 3 1432 664 0 0 1432 6...

Page 57: ...32 664 0 0 Seasonal space heating energy efficiency under colder warm er climate conditions 125 169 122 167 120 161 Water heating energy efficiency under colder warmer climate conditions 72 00 154 00...

Page 58: ...lass III 1 5 Class IV 2 Class V 3 Class VI 4 Class VII 3 5 Class VIII 5 Temperature control Seasonal space heating energy efficiency of heat pump 1 If tank rating is above A use 0 95 from fiche of boi...

Page 59: ...adjacent values 2 Prated is related to the preferential space heater or combination heater Tab 43 Package efficiency temperature regulator heat pump 200 ASL Hybrid 4 5MR AGC 15 AWHP 4 5 MR 200 ASL Hyb...

Page 60: ...12 Appendix 60 200 ASL HYBRID 7613348 v06 10122018...

Page 61: ...12 Appendix 7613348 v06 10122018 200 ASL HYBRID 61...

Page 62: ...12 Appendix 62 200 ASL HYBRID 7613348 v06 10122018...