background image

TO OPERATE

ON:

Tap the upper half of the rocker. The lights will turn ON.

OFF:

Tap the lower half of the rocker. The lights will turn OFF.

NOTE: To alert you that there is power to the switch when the load is OFF, the AC Indicator Light remains ON. To alert
you that the load is ON, the AC Indicator Light remains OFF.

NOTE: To alert you that the load is ON, the AC Indicator Light remains OFF. To alert you that the load is OFF, the AC
Indicator Light remains ON.

NOTE: If a power interruption should occur while the device is on, the light load will return to its previous state when
power is restored.

TESTING PROCEDURE

With Cat. No. 16293 properly wired and powered-up, tap the switch plate several times to ensure that the switch is
turning its load ON and OFF in response to manual control. Leave the switch in the ON position. Next, use a Cat. No.
6320, Leviton Table Top Controller, or any other controller, to check for proper switch operation as follows:

1. Transmit an OFF command to the switch. It should respond by turning its assigned Load OFF.

2. Transmit an ALL LIGHTS ON command to this switch from an appropriately coded controller. It should respond by

turning its assigned Load ON.

3. Transmit an ALL OFF command from an appropriately coded controller. It should respond by turning its assigned

Load OFF.

PERFECT PERFORMANCE CHECKLIST

If the Cat. No. 16293 appears to be functioning improperly proceed with the following steps:

1. Confirm that the 16293 is wired exactly as shown in the WIRING DIAGRAM.

2. Confirm that the switch is being supplied from a 120V, 60Hz AC source ONLY.

3. Confirm that the load being controlled is in proper working order. Local switch, ON (check for burned-out bulbs).

4. Confirm that the load being controlled does not exceed the 1200W switch limit.

5. Confirm that the switch’s Letter and Number codes are set correctly.

6. Confirm that the controller is powered and is set to transmit commands to the same letter and number code on the switch.

NOTE: If the switch still does not operate properly after following steps 1-6, the fault does not lie with the switch.
Proceed with steps 7 and 8.

7. Set the controller to transmit address P1. Using a Cat No. 6386 Signal Strength Indicator plugged in on the same

branch circuit as the controller, confirm that the controller is transmitting a minimum reading of 2 volts of command
signal at the HI-RANGE setting. If the signal strength is less than 2 volts, have the controller checked.

8. Check for adequate command signal at the Cat. No. 16293 location as follows:

A. Plug the Cat. No. 6385 Signal Test Transmitter into a receptacle on the same circuit as the controller.

B. Using the Cat. No. 6386 Signal Strength Indicator at the 16293 location, check the command signal amplitude.

Signal strength must be 100mV minimum. If there is less than 100mV of signal present, it may be necessary to
couple both legs of the 120/240 volt power service at the entrance panel using Cat. No. 6299 Signal Bridge.

C. If the Yellow ERROR CONDITION indicator is lit, there is electrical “noise” present on the AC line which is

interfering with proper module operation. The source of the noise must be identified and either filtered out or
eliminated (See Technical  Manual).

DI-000-16293-00D

Wiring Diagram 1 –  Single Pole Application

Incandescent / Fluorescent / Magnetic Low-Voltage

Wiring Diagram 2 – 3-Way Application

Incandescent / Fluorescent / Magnetic Low-Voltage

Hot (Black)

Neutral (White)

Black

Yellow

Black

White

Blue

Green

Ground

Line 

120VAC, 60Hz

Cap with 

Wire Connector

White

Universal

Switch

Load

(OR PRIMARY SIDE OF

MAGNETIC LOW-VOLTAGE 

TRANSFORMER)

}

Load

Hot (Black)

Neutral (White)

Universal

Switch

Blue

Blue

Yellow

Yellow

Green

Ground

Green

Ground

Black

White

Line 

120VAC, 60Hz

Multi-Remote

MSØØR-1

Black

White

(OR PRIMARY SIDE OF

MAGNETIC LOW-VOLTAGE 

TRANSFORMER)

}

DI-000-16293-00D

2/7/01, 3:55 PM

2

Reviews: