If the fire alarm is accepted, the field lights permanently red. After resetting of the fire alarm (using
RESET), the "FIRE" field returns to green.
The "FAULT" field behaves correspondingly in case of a fault, except here with a beeping from the
sounder. If the fault is accepted, the field lights up permanently yellow. After the resetting the fault
(once again using RESET), the "FAULT" field also returns to green.
If there are several new fire alarms or faults respectively, the relevant field ("FAULT", "FIRE") blinks
until all messages have been accepted.
If there are several accepted fire alarms or faults respectively, the relevant field remains illuminated
until all messages have been reset.
The "RESET" illuminated field can also turn from green to yellow for a short time. During this time, for
example, a system reset is being transmitted to a module and executed.
After a restart of the AFMS, the "RESET" field blinks until all modules and assemblies are initialised
(also in case a previously switched off loop is reconnected).
2.6.7.
"ALARM IN SEQU." illuminated field
ALARM IN SEQU.
In normal operation, the "ALARM IN SEQU." field is illuminated green. If there is more than one fire
alarm, the field turns from green to red.
When the fire alarms are reset except for one fire, the illuminated field changes back to green.
2.6.8.
"MAINS", "DISCONNECT", "PRE-ALARM" and "TEST MODE" illuminated fields
MAINS
DISCONNECT
PRE - ALARM
TEST MODE
In normal operation, all fields are illuminated green. In certain cases, these can also be illuminated
yellow.
·
MAINS
Fault in the power supply (mains or emergency power)
·
DISCONNECT Detectors, zones, loops or outputs are switched off
·
PRE-ALARM
Preliminary alarm at a smoke detector
·
TEST MODE
The AFMS is in test mode (one man test )