Operating instructions
Version 1.0
2018/03/17
page 12 of 24
2.6.5.
"FIRE"/"SILENCE", "FAULT"/”SILENCE” and "RESET" keys
FIRE
FAULT
RESET
A
A
A
Three keys are available for the user to process incidents such as a fire alarm or a fault.
·
FIRE/A
o
press 1st key: switch off signal (silence)
o
press 2nd key: accept fire alarm or
o
press 2nd key: open fire menu (required for a RESET)
·
FAULT/A
o
press 1st key: switch off signal (silence)
o
press 2nd key: accept fault or
o
press 2nd key: open fault menu (required for a RESET)
·
RESET
o
Reset fire alarm or fault
2.6.6.
"FIRE", "FAULT" and "RESET" illuminated fields
FIRE
FAULT
RESET
A
A
A
As normal operation, all fields illuminate green. If a new fire alarm occurs, the field "FIRE" lights up
red. The acoustic sounder emits a steady note.