Set damping time 

Density (to be used) 

Arbitrary  point  migration  input  compensation  value,  compensation 

value = P actual - P pre-output 

11 

LRV calibration 

12 

URV calibration 

17 

View Sensor Values 

 

Calibration of the instrument can be done as described in "7.1.4 Data Setting Method", with upper 
and lower range limits and damping settings. 
 
7.1.6 Unit Setting 
 
The units that can be set are: m, cm, mm, feet, and inch. 

 

①  Press and hold the '←┘' to enter the configuration mode (the No. 1 menu will be displayed first, 
and the up and down arrows on the left will be lit). 
②  Press the "↑" to switch the menu to No.2 and display the current unit symbol in the lower right 
corner. 

 

Unit Setting 

③  Press the '←┘' key again, the unit starts flashing units, now press the '↑' key or '↓' to switch to 
the unit you want to set. 
④ Press "←┘" again, the unit is set and the up and down arrows on the left side are lit. 

 

7.1.7 Range Setting 
 
Set the lower range LRV 
①  Press and hold the '←┘' key to enter the configuration mode (the No. 1 menu will be displayed 
first, and the up and down arrows on the left will be lit). 
②  Press the "↑" key to switch the menu to No.3, and the LCD will show the current LRV value. 

Summary of Contents for UQZ

Page 1: ...1 14 WWW DDTOP COM UQZ MAGNETIC FLOAT LEVEL TRANSMITTER Operation Manual UQZ DT JS 1004 2018 A...

Page 2: ...ut prior notice Quality Assurance Dandong Top Electronics Instrument Group Co Ltd guarantees that all glass plate level gauge have no defects in materials and manufacturing processes within one year f...

Page 3: ...sporting 5 2 5 Storage 5 3 Technical Characteristics 5 3 1 Product Features 5 3 2 Main Parameter 5 4 Dimension Schematic 6 5 Unpacking and Inspection 7 5 1 Matters needing attention in unpacking and i...

Page 4: ...ly safe or non flammable site operating procedures 1 2 Process leaks can cause serious injury or death Care should be taken to lift the transmitter If the process seal is damaged the medium may leak a...

Page 5: ...vel 2 3 Packing Please send the packaging waste to a special recycling agency 2 4 Hoisting and Transporting Please select qualified hoisting equipment and lifting straps and pay attention to safety 2...

Page 6: ...Medium temperature 40 120 Accuracy 10mm Power supply inlet M20 1 5 female thread or on request Explosion proof Intrinsic safety type Ex ia C T1 T5 T6 Ga Explosion proof type Ex d C T1 T5 T6 Gb IP rati...

Page 7: ...e appearance of the instrument is defective or damaged 6 Installation 6 1 Installation Tool Wrenches flange gaskets and flange bolts for process connections 6 2 Installation Technical Requirements 6 2...

Page 8: ...ng gasket 6 3 2 UQZ magnetic float level transmitter according to the following diagram to complete the wiring Figure 6 Figure 6 Wiring Diagram 7 Debugging 7 1 UQZ Magnetic Float Level Transmitter Deb...

Page 9: ...e Display 7 1 2 Description of LCD display symbols If you are in HART communication the symbol in the right corner of the LCD screen flashes LCD If the fixed output current is set the LCD will display...

Page 10: ...an switch between positive and negative sign of data 3 If you press the key again the first digit starts blinking when the selection of the symbol is finished it means the symbol bit can be modified T...

Page 11: ...mode the No 1 menu will be displayed first and the up and down arrows on the left will be lit Press the to switch the menu to No 2 and display the current unit symbol in the lower right corner Unit S...

Page 12: ...in 7 1 6 until the setting is complete 7 1 9 Two point Calibration LRV Calibration First adjust the PV value to the zero position the magnetic float toggles to the zero position Switch the menu to 11...

Page 13: ...ion value Compensated value PV actual PV pre output Note The key configuration process will not exit automatically you need to exit the key configuration manually The method is to press the key or key...

Page 14: ...Detect board damage Replace the damaged electronics on the test board No display on LCD screen remote transmission Damaged or poorly contacted ammeter Change the ammeter 10 Disassembly 10 1 Warning A...

Reviews: