background image

 

 

 

5

 

Pre-Installation Test

 

 
Before installing the system on your enclosure, it is a good idea to operate the 

unit for a few minutes to ensure it is functioning properly. Although the system has been 
tested at the factory, internal damage may have occurred during shipping which may not 
have been apparent during the unpacking inspection. This procedure will also help to 
familiarize you with the unit. 
 
1.  Place the system on a solid base such as a workbench or table. Be sure to allow for 
adequate space for airflow. There are two air streams that must not be restricted, the 
cold air stream and the warm air stream. Top mount units must be elevated to provide 
adequate airflow for the cold air stream located on bottom of system. Check the Model # 
to determine whether it’s a Top or Side mount air conditioner. 

Top mount units can 

only be mounted on a flat horizontal surface and Side mount units can only be 
mounted on a flat vertical surface. 

 

2.  Check that the warm air system filter is in place. (Location varies with model type) 

*

Models with the optional rain or wash down hood do not have this filter and 

require regular condenser maintenance.

 

 

3.  Check the data tag for proper electrical requirements. The data tag will give the 
voltage and amperage requirements of the system.  Be sure the electrical outlet where 
the system will be connected has the proper capacity.  After noting the above, connect 
the power cord to a properly grounded electrical outlet. An extension cord is not 
recommended.

 

** If any unusual noise or vibration is present during the testing procedure, immediately 
disconnect the power cord and inspect the unit for the cause of the noise or vibration and contact 
Ice Qube immediately. 

 

4.  As soon as power is supplied to the system, the cold air evaporator blower will 
begin operation. The compressor and warm air condenser blower will not operate 
if the room air temperature is below 80’ F. This is because the temperature 
controller has a factory set point of 80’ F. 

(The digital display on the face of the 

controller will be displaying room temperature.) If the display is indicating 80’ F or 
warmer, the cool status LED will flash for 3-1/2 minutes before the compressor and 
warm air condenser blower will operate. 
 
If the display is indicating a temperature less than 80’ F, you must change the set point 
to a temperature lower than the room temperature in order for the compressor and warm 
air condenser blower to operate.  (Refer to the section on the Temperature Controller in 
this manual.)     

 

 5.  With the compressors and both blowers operating, allow the unit to operate 
for 20 to 30 minutes. This will provide sufficient time for the vapor compression 
system to achieve operating balance. Measure the cold air outlet temperature 
with an accurate thermometer. This temperature should be at least 10’ F colder 
than the inlet air temperature if the room temperature is warmer than 70’ F.  Inlet 
air temperature will be displayed on the temperature controller.

 

(In areas where 

the humidity is high, the temperature difference may be less than 10’ F.) 

 
6.  After completing these few simple checks, you are ready to prepare the electrical 
enclosure for installation of the unit.

 

 

 

 

 

Summary of Contents for AIR CONDITIONER SYSTEMS

Page 1: ...1 AIR CONDITIONER SYSTEMS FOR ELECTRONIC ENCLOSURES OPERATIONS AND INSTALLATION MANUAL ...

Page 2: ...uture reference Some information may not apply to your system Where To Find Information On Introduction Page 3 Basic Operation Page 4 Unpacking Inspection Page 4 Pre installation Test Page 5 Preparing The Enclosure Page 6 Operating Your System Page 7 Programming The Controller Page 8 Alarm Operation Page 9 Maintenance Page 10 Troubleshooting Page 11 Schematic Wiring Diagram Page 12 Warranty Back P...

Page 3: ...etically pleasing package requiring minimal maintenance The closed loop circulation design also protects your equipment from air borne dust and contaminants which may hinder your equipment operations and cause unnecessary downtime DDB offers models ranging in cooling capacity from 1 000 to 20 000 BTU per hour to provide cooling systems for many of your conditioning needs DDB also offers select mod...

Page 4: ... enclosure through a filter and across the warm air heat exchanger Here heat from the enclosure is transferred from the warm air heat exchanger to the warm air stream and dissipated to the ambient Unpacking Inspection What to look for 1 Shipping container is banded to the pallet and arrows on the shipping container are pointing in the proper upward direction The system is position sensitive DDB re...

Page 5: ...ended If any unusual noise or vibration is present during the testing procedure immediately disconnect the power cord and inspect the unit for the cause of the noise or vibration and contact Ice Qube immediately 4 As soon as power is supplied to the system the cold air evaporator blower will begin operation The compressor and warm air condenser blower will not operate if the room air temperature i...

Page 6: ...e the modifications to be made to the enclosure using a marking pencil Note the boltholes cutouts for the inlet and outlet air streams and the power cord 4 Make the holes for the studs bolts and power cord using a drill Bit size will vary with model Be sure to protect any equipment located within the enclosure from debris produced during the installation procedure 5 Drill a pilot hole for a saber ...

Page 7: ...air blower start This signifies that the cooling system has begun operation to remove heat and humidity from within the enclosure It may take 20 to 30 minutes operating time to reach full capacity If the heat load within the enclosure is less than the BTUH capacity of the of your Ice Qube system you will notice the temperature on the digital display begin to decrease When the temperature inside th...

Page 8: ...rm settings Press the Select 3 button to continue The set alarm hi LED is on with the display indicating the high temperature alarm set point The alarm will activate at this temperature and will automatically reset at 2 degrees Fahrenheit 1 degree Celsius below this temperature Press the Adjust up 1 or Adjust down 2 arrow to change the alarm set point in a range from 8 degrees Fahrenheit 4 degrees...

Page 9: ...re installed on your system no filter is supplied with your system and the filter alarm should be set to 0 This will disable the filter alarm Press the Select 3 button to continue Making adjustments to this setting is necessary only for installation of the ICENET communication network Omit this otherwise The program LED will be lit and the display will show Add This is where you will program the n...

Page 10: ...order to prevent prolonged cooling system downtime The dirty filter may be cleaned at a more convenient time 2 Condensate Management System The condensate management system should be checked periodically for scale sludge and debris which may cause the system to fail On open type enclosures and in areas where the enclosure door is opened frequently in dirty or industrial environments maintenance sh...

Page 11: ...ould occur please make the following simple checks before contacting DDB Is electrical power available at the outlet Is the power cord plugged into the outlet Is the controller set point temperature above the enclosure temperature Is the evaporator cold air stream blower operating Is the compressor and condenser warm air stream blower operating Is the enclosure door closed tightly Are all gaskets ...

Page 12: ...tify the seller of such defects whether patent or latent within the Warranty Period Seller shall have no further liability or obligation to the Buyer Therefore in no event shall Seller s liability under this warranty exceed the original purchase price of the products which are the subject of a proper notice of defects Excluded from this transaction are all implied warranties including without limi...

Reviews: