Chapter 3

Testing

Overview

The PTT24 has a front panel test switch, Channel Selector Switch for the Guard Channel, 
Audible Alarm, and LEDs. The PTT24 has rear panel Alarm IN and Alarm OUT connectors. 
The PTT24 has an internal RS232 test port. A factory test assembly is used during 
manufacturing for final testing of the PTT24. Most of the PTT24 functionality can be checked
in the field. The following outlines the testing that can be done in the field. The factory test 
procedures are also noted. The factory test assembly can be purchased for customer field use. 

Field Testing

Front Panel Test Switch

Pressing the front panel test switch will enable all the relays, sound the audible alarm, light 
the Alarm LED,  cause the Alarm Out leads to close and all the relays will operate. The 
sound of the relays operating can be heard as a low level clicking sound. The alarm will 
sound only when the ALARM toggle switch is in the ON position.

Alarm In and Alarm Out

To test the Alarm In, the 2 leads on the Alarm In connector can be shorted together. When 
shorted, the ALARM LED will light, the audible alarm will sound (if not disabled by the front
panel switch) and all the relays will operate. The Alarm Out can be checked with a VOM. 
When the the Relay Test button is pushed the Alarm Out leads will be closed.

Channel Selector Switch and Power LED

  

The channel selector switch can be set to an invalid channel number. This will cause the 
Power LED to flash. 

Audible Alarm

With the Alarm Cutoff Switch set to ON, pressing the Test Switch will cause the audible 
alarm to sound. Also, shorting the Alarm In leads will cause the audible alarm to sound. If 
the alarm is activated with the Alarm Cutoff Switch set to OFF, no audible alarm will sound.

LEDs

The LEDs are Power/Invalid Channel, ACO and Alarm. The Power LED is on when power is 
applied to the PTT24. The Power LED will flash if an invalid control channel is selected. An 
invalid channel is any except 1 through 12 when 12 channels are selected via the front panel 
switch. An invalid channel is any except 1 through 24 when the 24 channels are selected via 
the front panel switch. 

RS232 Port

The PTT24 has an internal RS232 port located on the right hand side of the PC board when 
viewed from the front. To access the RS232 port the cover of the PTT24 must be removed. 
The RS232 port is an RJ45 connector. A special Network Management cable and RJ45 to  
DE-9 female connector is available for using this RS232 port. See the next section for details 
on the operation of the RS232 port.

9

Summary of Contents for PTT24

Page 1: ...24 Manual Copyright 2016 All rights reserved Manual version 1 0 Firmware version 1 0 All trademarks and trade names are the properties of their respective owners July 2016 Manual Version 1 0 Firmware...

Page 2: ...llation and Configuration 4 1 Rack Mounting 4 2 Cabling 4 12 and 24 Port cable reference 5 3 Select 12 or 24 ports 6 4 Chassis grounding 6 5 Power connections 7 6 Alarm connections 7 7 Select control...

Page 3: ...pe III is not supported In the PTT 24 12 channel mode selecting control channel 1 through 12 will select one of the even numbered leads 26 though 48 as the control channel The other 11 even numbered l...

Page 4: ...software to configure or operate the PTT24 Using the PTT24 RS232 port requires removing the top cover to access the management port located inside the unit Except for testing it should never be necess...

Page 5: ...nual Chapter 2 Installation This Chapter details the installation process Overview The PTT24 is a 1U high by 19 rack mount unit Installation and configuration of the PTT24 PTT24 Front Panel PTT24 Rear...

Page 6: ...nt panel from being bent or scratched by the mounting screws 2 Cable the Channel Bank to the PTT24 Standard straight through 50 pin male to female telco cables are used to connect to the PTT24 The PTT...

Page 7: ...PTT24 Manual Controlled and Pass Thru Channels for the 12 and 24 Channel Selections 5...

Page 8: ...channels of E M leads to be controlled by the PTT24 The left position selects 24 channels the right position selects 12 channels 4 Connect the PTT24 Frame Chassis Ground Frame ground is on the 48 VDC...

Page 9: ...connected to another PTT24 to a SCADA system for remote reporting to some local external alarm signal device etc The Alarm In and Alarm out are contact closures Alarm Off is open Alarm On is a closed...

Page 10: ...Relay Test switch can be pressed for a quick test The audible alarm should sound relays should click the Alarm LED should light the Alarm Out relay should operate The alarm will sound only when the AL...

Page 11: ...ll the relays will operate The Alarm Out can be checked with a VOM When the the Relay Test button is pushed the Alarm Out leads will be closed Channel Selector Switch and Power LED The channel selecto...

Page 12: ...low ACO LED to indicate the ALARM CUT OFF is on Rear Panel 2 rear panel power inputs for 48 VDC power diode protected between the 2 power inputs to avoid power feed back Alarm Input dry contact closur...