9
Programming Menu
To select the panel operating logic, access the programming menu by pressing the buttons
SETUP
,
UP
and
DOWN
at the same time on the main screen of the panel.
User Menu
On completion of panel operation programming, enter the setup menu to configure the
various data for motor start-up. To access the user menu, press the button
SETUP
for 4
seconds in the main screen of the panel.
Language
0 ITA / 1 ENG/ 2 FRA
Number of Pumps
This parameter enables selection of the number of pumps in the system
(when 1 single pump is selected, the parameter PUMP ROTATION
ENABLED is disabled).
DESCRIPTION OF PARAMETER
VALUE
Operating Logic
0
FAULT
0
2
-
1-4
As per order
Pump rotation enabled
This parameter enables activation of pump exchange on each demand
from floats or pressure switches. Also, if the main pump thermal cutout
(current overload) trips, the second pump is enabled.
Sensor Sensitivity (Sa - Sb - Sc - Sd)
This parameter enables display of sensor sensitivity. With the contacts open,
if a value of 99 is displayed, and a value of 45 is displayed with water
present, set sensitivity to an intermediate value, such as 75.
Minimum Level Alarm Output
This parameter enables removal of the minimum level alarm from the
cumulative alarm output.
Y or N
Y
0-99
75
Y or N
Y