background image

The sensor module has M12-male connector which is matched with M12-female connector on wireless module;

Carefully plug the sensor module onto wireless module, using 

HAND

 to tighten slowly until stop;

Note: please 

DO NOT

 over tightening by hand or other tool, it can damages the M12 connector;

Steps for battery installation:

Using Philips screw driver to unscrew M2 screw at the side of housing

Carefully pull out the top plastic housing in the vertical direction

7.4 Power Supply & Battery installation

Summary of Contents for WS433-M12F-ATH

Page 1: ...ensor to deliver high accuracy and stable measurement The wireless portion is Sub GHz technology from Texas Instruments allows long range transmission at ultra low power consumption It will connect 2 way wirelessly to the wireless co ordinator WS433 CL to send data and receiving the configuration It can be configured the operation parameters like data sending interval health check cycle remotely f...

Page 2: ...ical connection M12 male connector WIRELESS TRANSMITTER SPECIFICATION Data speed Up to 50kbps Tranmission distance LOS 1000m Antenna Internal Antenna Battery 01 x AA 1 5 3 6VDC up to 10 year operation depends on configuration Frequency Band ISM 433Mhz Sub GHz technology from Texas Instrument USA International Compliance ETSI EN 300 220 EN 303 204 Europe FCC CFR47 Part15 US ARIB STD T108 Japan Viet...

Page 3: ...0oC with AA L91 Energizer Housing Poly carbonate IP67 Installation method L type bracket SUS304 by M4 screws or double sided 3M tape included Product dimensions weight 125x30x30mm 60g without battery Box dimension gross weight 190x50x50mm 100g 4 Product Pictures ...

Page 4: ...measurement For example the measurement time is 200mS after this time the node will read the value of sensor using I2C node will switch OFF power supply to external sensor to save energy Once reading the sensor value the raw data is X it can be scaled to any engineering value by the following formula Y aX b Where X the raw value reading from output of sensor before calibrated validated Y the calcu...

Page 5: ...ow threshold 1 Hi Byte of Logic status 0 If parameter 1 is digital Hi Byte of Logic status parameter 1 s value Timer up 1 Total time when Hi Byte of Logic status 1 Timer down 1 Total time when Hi Byte of Logic status 0 RisingEdge counter 1 Counter value when Hi Byte of Logic status changes from 0 to 1 FallingEdge counter 1 Counter value when Hi Byte of Logic status changes from 1 to 0 Lo Byte is L...

Page 6: ...ks long range wireless co ordinator ws433 cl page user guide for long range wireless co ordinator ws433 cl Locate the place where the wireless sensor is mounted from that locate the position to mount the bracket Placing the wireless module on bracket and secure it by 02 x M2 screws supplied in accessory bag Note The bracket can be mounted on the wireless module in both direction upward or downward...

Page 7: ...te metallic box or housing The RF signal can not pass through metallic wall This wireless module would be installed a semi metallic box because the RF signal can pass through the non metal wall are The best case is to install the wireles module inside or Non metallic box Some non metallic materials plastic glass wood leather concrete cement 7 2 Installation location 7 3 IO Wiring Sensor installati...

Page 8: ...ess module usingHAND to tighten slowly until stop Note please DO NOT over tightening by hand or other tool it can damages the M12 connector Steps for battery installation Using Philips screw driver to unscrew M2 screw at the side of housing Carefully pull out the top plastic housing in the vertical direction 7 4 Power Supply Battery installation ...

Page 9: ...uch pulling force at the beginning therefore please do it carefully to avoid the damage of circuit board which is very thin 1 00mm Insert the AA battery please take note the poles of battery Insert the top plastic housing and locking by M2 screw ...

Page 10: ...rect Check that the battery is empty or not installed correctly Reconfigure the RF data rate with the button according to the instructions Manufacturer Daviteq Technologies Inc No 11 Street 2G Nam Hung Vuong Res An Lac Ward Binh Tan Dist Ho Chi Minh City Vietnam Tel 84 28 6268 2523 4 ext 122 Email info daviteq com www daviteq com Distributor in Australia and New Zealand Templogger Pty Ltd Tel 1800...

Reviews: