background image

2

Failed to add auto

sensor

When the first 5 minutes are

up, the sensor cannot be

added

Node needs to be added

further away from WS433-CL

The iConnector and the node

are configured to run at 2

different RF frequencies, or

different data rates

Unplug, wait 10 seconds, plug in

again to enable automatic add or

write to modbus

Enb_auto_add_sensors = 1

Bringing nodes and iConnector

together or temporarily setting

the smaller Rssi_threshold can

add sensors farther (then return

the old values)

Check the RF frequency, data rate

of iConnector and the node

3

Read modbus normal

health values but read

the data of the node, all

are 0

The modbus 4 command

only supports FW 1.9, old

FWs can't read command 4

Check the FW of WS433-CL in

iConnector if it is older than 1.9

then use command 3 to read data

and other registers

4

The node's data has no

data of prm1 and prm2

The sensor attached to the

node is loose

For the WS433-M12F node, if

the sensor is attached after

the battery is attached to

the node, the sensor type

may be different so the data

cannot be read.

Attach the sensor to the node

firmly

Attach the sensor to the WS433-

M12F node first. Then remove the

node pin, wait for 10 seconds, re-

attach to the node to re-identify

the sensor

5

Status led of iConnector

doesn’t light

No power supply

Check if the power cable is

disconnected

Check if the connector of

iConnector is loose or

disconnected

6

Mobus led of iConnector

doesn’t light

No RS485 connection

Check if the signal cable is loose

or disconnected

7

Network led of

iConnector doesn’t light

No network connection

Check if the power cable is

disconnected

Check if the connector of

iConnector is loose or

disconnected

Distributor in Malaysia

AVO Technology Sdn. Bhd.

Official Website: www.avo.com.my

No. 17, Jalan 3/23A, Taman Danau Kota, 53300 Kuala

Lumpur, Wilayah Persekutuan Kuala Lumpur, Malaysia

General : +603-4143 2288

Mobile : +012-376 7181

Fax : +603-4143 3388

Distributor in Australia and New Zealand

Templogger Pty Ltd

Tel: 1800 LOGGER

Email: [email protected]

Manufacturer

Dai Viet Controls & Instrumentation Company Ltd.

No.11 Street 2G, Nam Hung Vuong Res., An Lac Ward, Binh Tan Dist., Ho Chi Minh City, Vietnam.

Tel: +84-28-6268.2523/4 (ext.122)

Email: [email protected] | www.daviteq.com

 

9. Support contacts

Summary of Contents for iConnector

Page 1: ...USER GUIDE FOR ICONNECTOR 3G INTEGRATED WIRELESS CO ORDINATOR STHC ISG02DB WS433 CL 04 Smart IoT Gateway iConnector ...

Page 2: ...ols This iConnector is build in a wireless co ordinator in a wireless sensor network a high performance type to facilitate remote configuration and diagnostics as well as remote monitoring and control via any IIoT platform It is able to configure the parameters for all end nodes in the network By the Sub Ghz technology from Texas Instruments it is easy to establish multiple networks in same area wit...

Page 3: ...12 female 4 pin A coding Buzzer Internal buzzer Back up battery Lithium Super Capacitor RF frequency band Free license ISM 433 92Mhz for others 868 915 920Mhz refer related datasheets Ready to comply ETSI EN 300 220 EN 303 204 Europe FCC CFR47 Part15 US ARIB STD T108 Japan Vietnam Type Approval Certification QCVN 73 2013 BTTTT QCVN 96 2015 BTTTT DAVITEQ B00122019 Security Standard AES 128 Operatin...

Page 4: ...Box dimension W160 x D150 x H100 mm Gross weight 300g 4 Product Pictures ...

Page 5: ...gnet near the Hall sensor for 5s see the LED blink twice or the buzzer beep 2 Beep release the push button or take the magnet to set Data rate RF 625bps Press and hold the push button or bring the magnet near the Hall sensor for 10s see the LED blinking 3 times or the buzzer buzzes 3 Beep release the push button or take the magnet to perform the User factory reset User factory reset reset frequenc...

Page 6: ...ifically as follows Co ordinator_ID parameter in the memap of WS Co ordinator s ID Receive data packet from node When WS433 CL receives data packet from node then WS433_CL will send back 1 ACK packet Standard data packet received includes 46 bytes Name Size bytes Format Battery 2 uint16 Main parameter 4 err_status 1 uint8 sen_status 1 uint8 Second parameter 4 Logic status 1 1 uint8 Logic status 2 ...

Page 7: ...0 32 data node 29 928 3A0 32 data node 30 960 3C0 32 data node 31 992 3E0 32 data node 32 1024 400 32 data node 33 1056 420 32 data node 34 1088 440 32 data node 35 1120 460 32 data node 36 1152 480 32 data node 37 1184 4A0 32 data node 38 1216 4C0 32 data node 39 1248 4E0 32 data node 40 Control from WS433 CL to node Using the modbus 16 command to write down the control area WS433 CL will send th...

Page 8: ...rl node 19 2152 868 8 ctrl node 20 2160 870 8 ctrl node 21 2168 878 8 ctrl node 22 2176 880 8 ctrl node 23 2184 888 8 ctrl node 24 2192 890 8 ctrl node 25 2200 898 8 ctrl node 26 2208 8A0 8 ctrl node 27 2216 8A8 8 ctrl node 28 2224 8B0 8 ctrl node 29 2232 8B8 8 ctrl node 30 2240 8C0 8 ctrl node 31 2248 8C8 8 ctrl node 32 2256 8D0 8 ctrl node 33 2264 8D8 8 ctrl node 34 2272 8E0 8 ctrl node 35 2280 ...

Page 9: ...s to change configuration on node Use modbus RTU command 16 write to configuration area on WS433 CL sync status 1 WS433 CL wait for node to send data When node send data up then WS433 CL will send the configuration to node node sends back authentication ACK containing this new configuration part sync status 0 sync configuration OK user should read this configuration again to check if it s correct ...

Page 10: ... bring the sensor closer to the co ordinator s antenna until the peep sound is heard that the sensor has been added to the co ordinator If you do not hear the Peep sound please remove the power and try again Step 1 Open Modbus tool on PC You can download Daviteq Modbus Configuration Tool Version 1 2 with the following link http filerun daviteq com wl id RtuE0i9N8KNJ8fTVdHv4DcJEHdaDcetp Unzip TOOLS...

Page 11: ...R433_V1 6 csv This file is attached in the zip file Step 2 Check information of sensor after adding S N of each sensor Configuration Protocol Modbus RTU Address 1 247 Baud rate 4800 9600 19200 115200 Parity none even odd Stop bits 1 Memmap resgisters You can download Modbus Memmap of WS433 CL FW_V1 9 with the following link http filerun daviteq com wl id q64HsdUTIamRdNWIIi7kiBdrcJbmhCkX The mounti...

Page 12: ...ease pay attention to the following conditions DO NOT install the wireless module inside a completemetallic box or housing The signal can not pass through metallic wall This wireless module would be installed a semi metallic box because the RF signal can pass through the non metal wall are The best case is to install the wireless module inside or Non metallic box Some non metallic materials plasti...

Page 13: ...tion slave address baudrate parity is not correct Reading the wrong command wrong address register Check the power connection Check the connection modbus A B Check the configuration of slave address baudrate parity iConnector only supports modbus 3 4 and 16 Check if the value of modbus status returned by 2 or 3 is an incorrect address reading 8 Troubleshooting ...

Page 14: ...nt so the data cannot be read Attach the sensor to the node firmly Attach the sensor to the WS433 M12F node first Then remove the node pin wait for 10 seconds re attach to the node to re identify the sensor 5 Status led of iConnector doesn t light No power supply Check if the power cable is disconnected Check if the connector of iConnector is loose or disconnected 6 Mobus led of iConnector doesn t...

Reviews: