background image

 

For this type of alarm to be valid, the parameter of interest must pass 
through both thresholds within the specified time period.  If the parameter 
is between the thresholds when the alarm is set, or above the higher 
threshold for an upward trend alarm or below the lower threshold for a 
downward trend alarm, the alarm will not become active.  Please note 
that frequent communication with the data logger will cause the timing 
function of this alarm type to run long. 
 
For guidance on how to use this alarm, it may be best to consult 
historical weather data from WeatherLink plot data (or other sources) to 
determine what kind of behavior a parameter exhibits before 
approaching a value of concern.  Make note of how quickly the value 
changes over time before it reaches that value.  These changes will 
govern your threshold values and  time period.  Your second threshold 
probably should not match this value, but rather be lower than this value 
for a upward trend alarm and higher than this value for a downward trend 
alarm. 

 
 

 

= (

Equal) This can be used to check whether any value is exactly equal 

to the set threshold value. 

 

 

 

 

Minus

 or “Difference” alarm allows you to compare the difference 

between two like variables.  For this check type, the two variables must 
be measured in the same units of measure in order to be compared.  If 
this check type is selected, the software will use the parameter pick list 
on the row below for the second of the two like variables to indicate.  
Enter a positive difference you want to compare in the available edit box 

15

Summary of Contents for WeatherLink

Page 1: ...d Guide and on line Help files for information on the use of the WeatherLink program including its hardware requirements and typical installation package contents and optional accessories for this pro...

Page 2: ...as WeatherLink if you ever need to install the program manually Running the Configuration Software To run the configuration software double click on the Streaming Data Utility icon in the Streaming Da...

Page 3: ...ata logger connected to your system it is highly recommended that you manually set the Com Port and Baud Rate Logger Type The software indicates the logger type and firmware revision level of the stre...

Page 4: ...ave an output open or closed You may adjust this value if you want the alarm checking functions to resume later after communicating to the logger using WeatherLink or the Streaming Data Utility Press...

Page 5: ...olar Radiation and UV check boxes You can also check them separately The Leaf Wetness Soil Moisture Leaf Temperature and Soil Temperature selections refer to the sensors on the Leaf Soil Moisture Temp...

Page 6: ...smitter ID 1 and a Temperature Humidity Station on ID 4 and a Temperature Station on ID 2 you would check the following dialog boxes in the example shown below There is no need to indicate your ISS Te...

Page 7: ...ts of measure displayed on the console which may be changed independently of this software You may select from the following settings Temperature Fahrenheit F or Celsius C Note Wind chill dewpoint deg...

Page 8: ...rical device This function is used to test the output of the Alarm Output data logger Push the button of the output you want to test The button will be depressed to indicate Closed circuit mode and ra...

Page 9: ...directory When download is complete the text file will automatically open The log will consist of which output became active which parameters caused the alarm to become active useful for the AND type...

Page 10: ...it is deactivated The default value is zero Frequent communication with the data logger will cause this function to run long Pulse Width This function determines the pulse width for any of this selec...

Page 11: ...utput data logger to leave an electrical device OFF unless an alarm condition occurs Choose normally closed if you want the Alarm Output data logger to leave an electrical device ON unless an alarm co...

Page 12: ...Then select what type of test condition you want to check it against A Greater Than or or high alarm checks for greater than or equal to A Less Than or or low alarm checks for less than or equal to 12...

Page 13: ...A Between alarm checks to see if the current value is between the two threshold values A Not Between alarm checks to see if the current value is not between the two threshold values 13...

Page 14: ...g a value of concern It is like a predictive alarm If the number you enter in the first edit box is lower than the number you enter in the second box the data logger will check for an upward trend Lik...

Page 15: ...aching a value of concern Make note of how quickly the value changes over time before it reaches that value These changes will govern your threshold values and time period Your second threshold probab...

Page 16: ...F Inside Temperature Minus Outside Temperature IS Greater Than or 5 0 F AND Inside Temperature IS Greater Than or 70 F DONE 2 A user wants to activate their sprinkler system when the Daily ET exceeds...

Page 17: ...onditions Choose DONE if this is the only condition you want to check Choose OR if you want this condition or any of the other conditions you set to trigger an alarm Choose AND if you require this con...

Page 18: ...be powered for at least 10 minutes to utilize a valid wind chill value Dewpoint formula is also the same as what the Vantage Pro and Vantage Pro2 console uses but this has not changed from the origina...

Page 19: ...e device it is not subject to arcing and contact welding as are mechanical relays However since it is a solid state device it will be damaged by operation beyond its ratings which are Nominal Load Vol...

Page 20: ...Product Number 06544 Davis Instruments Part Number 07395 219 WeatherLink for Alarm Output Rev A Addendum 08 30 05...

Reviews: