IPDU-A Series User Manual
17
.
Ⅹ
Technical Specification
No.
Item
Parameters
1
Input
Single
phase
Rating voltage
110/220V 50/60HZ
The max current
16A
、
32A
、
63A
Three
phase
Rating voltage
380V 50/60HZ
The max current
3×16A
、
3×32A
Direct
current
Rating voltage 240V /336V
The max current 40A / 60A
Cable Spec
16A
:
3×2.5mm
2
×3M 32A
:
3×6.0mm
2
×3M
63A
:
3×16.0mm
2
×3M
3×16A
:
5×2.5mm
2
×3M 3×32A
:
5×6.0mm
2
×3M
Input terminal
16A input
:
3×2.5mm
2
×3M IEC60320 C20 input
32A input
:
3×6.0mm
2
×3M IEC60309 industrial plug
63A input
:
3×16.0mm
2
×3M IEC60309 industrial
plug
3×16A input
:
5×2.5 mm
2
×3M IEC60309 industrial
plug
3×32A input
:
5×6 mm
2
×3M IEC60309 industrial
plug
Overload protector
Circuit breaker
(
optional
)
2
Output
Single
phase
Rating voltage
110/220V
The max
current
16A
、
32A
、
63A
Three
phase
Rating voltage
220V
The max
current
3×16A
、
3×32A
Direct
current
Rating voltage 240V /336V
The max current 40A / 60A
Outlet standard
Optional
Outlet quantity
Optional
3
Display
Display method
LCD display
Display contents
Amps/volts/kWh/kW, IP address, address code, the
temperature/humidity
Accu
racy
Voltage
Accuracy
:
±(1
﹪
+3byte)
Resolution
:
1V Respond time
:
400ms
Display method
:
LCD; Display direction
:
Vertical
Current
Accuracy
:
±(1
﹪
+1byte)
Resolution
:
100mA Respond time
:
400ms
Display method
:
LCD; Display direction
: