DT1364
22
20171206-V0
9. Appendix
9.1. Technical specification
Intrinsical safety data
Certification:
BKI 14 ATEX 0012, BKI 14 ATEX 0012/1
Marking:
II (1)G [Ex ia Ga] IIC/IIB (-20 °C
≤
Ta
≤
+50 °C)
II (1)D [Ex ia Da] IIIC (-20 °C
≤
Ta
≤
+50 °C)
Safety data: DT1364
IIC
IIB
Uo
Io
Po
Co
Lo
Co
Lo
Limit outputs safety data:
8.61 V
11.6 mA 24.96 mW
2 µF
100 mH
20 µF
200 mH
Um: 250
Veff
Input parameters:
Number of inputs:
2
In compliance with the standard EN 60947-5-6 (NAMUR):
No load voltage:
8.2 V
Short circuit current:
8.2 mA
Input resistance:
1000 ohm
Low-current input version, upon request:
No load voltage:
8.2 V
Short circuit current:
0.5 mA (max.)
Input resistance:
18 kohm
Output parameters:
Number of outputs:
2
Contacts: SPDT
contact
Contact rating:
250 VAC, 5 AAC, 500 VA or
30 VDC, 5 ADC
Galvanic isolation:
Operating isolation voltage:
250 Veff (between the input, the output,
and the supply voltage terminals)
Test voltage:
2500 VDC (between the input and the
output terminals; between the input and the
power supply terminals)
Power supply:
Supply voltage:
19-29 VDC
Consumption: 2.1
W
Summary of Contents for DT1364
Page 1: ...DT1364 Intrinsically Safe NAMUR Contact Isolators Operating Instructions...
Page 24: ...DT1364 24 20171206 V0 9 2 Application example...
Page 25: ...DT1364 20171206 V0 25 9 3 ATEX Certification...
Page 26: ...DT1364 26 20171206 V0...
Page 27: ...DT1364 20171206 V0 27...
Page 28: ...DT1364 28 20171206 V0...
Page 29: ...DT1364 20171206 V0 29...
Page 30: ...DT1364 30 20171206 V0...
Page 31: ...DT1364 20171206 V0 31...
Page 32: ...DT1364 32 20171206 V0...
Page 33: ...DT1364 20171206 V0 33...
Page 34: ...DT1364 34 20171206 V0...
Page 35: ...DT1364 20171206 V0 35...
Page 36: ......