background image

 
 

Model K-415A 

 

 

Page 2 

CAUTION

  

Connect the K-415A to a suitable A/C source and each outlet on the K-415A to the devices to be 
controlled.  
 
The maximum current rating for all of the devices connected to the K-415A cannot add up to more than 
15 amps  in domestic NEMA applications, or 10 amps in International applications as determined by the 
IEC connector and the line cord. 

See the specifications for each version on the following page.

  

 
The K-415A provides 5 indicator lamps.   

POWER :    Indicates that A/C power is applied to the K-415A 
CIRCUIT:    (CKT)  Indicates which of the four outlets is ON  
 

 
 
 
 
 
 
 
 
 
 
 

 

SPECIFICATIONS 

 

K-415A  

     MAIN POWER INPUT:  Standard NEMA 5-15 Plug on  6 foot 14/3 line cord  - 120VAC 
     OUTPUT CIRCUITS: Standard NEMA 5-15 Receptacle 
     CURRENT MAXIMUMS:  15 Amps per Receptacle 
 

 

 

           15 Amps combined total of all receptacles  

 

K-41OA-IEC

   

     MAIN POWER INPUT:  IEC 320 Male Connector – 220 -230 VAC  
     OUTPUT CIRCUITS:     IEC 320 Receptacle 
     CURRENT MAXIMUMS:  10 Amps per Receptacle 
 

 

 

           10 Amps combined total of all receptacles 

 
 
    PHYSICAL:     1.75 H,  8.75 D   19.0  EIA Rack mount   (inches)  
                           Weight: 
 
 

 

 

 

K-415A  Rear View  - Standard NEMA Version 

1

2

3

4

CONTROL

15A Fuse

 

CONTROL WIRING:

   9 pin female  d-subminiature  

 
 Contact Closure between Control to Com = Power OFF 

 
 CONTROL #  PIN #            FEEDBACK#   PIN # 

       1                1                         1                6 
       2                2                         2                7 
       3                3                         3                8 
       4                4                         4                9 
     COM            5                       COM           5 

Reviews: